The RT510TX thermostat will switch your heating system on or off, as needed, in accordance with the time and temperature set by you. It can be used with the RXBC605 integral plug-in RF boiler control. The RF boiler control is a direct replacement for the basic time clock or blanking plate usually supplied with the boiler. Installing the RF boiler control takes minutes. Once installed, you will benefit from all the control features of the RT510TX thermostat.
This product complies with the essential requirements and other relevant provisions of the following EU Directives: EMC 2014/30/EU, LVD 2014/35/EU, RED 2014/53/EU and RoHS 2011/65/EU. Full text of the EU Declaration of Conformity is available on www.saluslegal.com
868.0-868.6MHz; <13dBm
Use in accordance with the regulations. Indoor use only. Keep your device completely dry. Disconnect your device before cleaning it with a dry cloth. This accessory must be fitted by a competent person, and installation must comply with the guidance, standards and regulations applicable to the city, country or state where the product is installed. Failure to comply with the relevant standards could lead to prosecution.
Always isolate the AC Mains supply before installing or working on any components that require 230 VAC 50Hz supply.
Terminal | Identifier | Description |
1 | N | Neutral |
2 | L | Live input (230V AC) |
3 | COM | Common terminal (volt free) |
4 | N.O. | Normally Open |
LED - It will be on when the thermostat is demanding heat.
SYNC Button - This is used only for pairing the RF communications.
Mode Switch
The AUTO / MANUAL
switch allows you to turn on the Boiler Control manually if required.
When the thermostat is operating in NORMAL mode, if the Boiler Control has not received a signal from the transmitter after 1 hour, the Boiler Control will turn off the boiler, and the LED indicator will flash constantly (two times every second). Once the Boiler Control receives a valid ON or OFF signal, the Boiler Control will control the heating system accordingly.
Key | Function |
![]() |
|
![]() | Press once to activate/deactivate Boost function |
![]() | Press once to enter/exit Permanent Override function |
![]() | Increase button |
![]() | Decrease button |
![]() | Select the clock or programme settings |
![]() | Press to confirm your settings |
![]() |
|
![]() | Press the buttons for 3 seconds to enter Installer Mode |
![]() | Press the buttons for 3 seconds to enter Clock Settings |
The DIP Switches can be found on the rear of your thermostat.
Control feature | TPI | Span |
Operation | When TPI is selected on DIP switch № 2, the DIP switch № 1 is functional. You can choose the Cycles Per Hour between a lower comfort level (6CPH) and a higher comfort level (9CPH). | When Span is selected on DIP switch № 2, the DIP switch № 1 is not functional. The temperature accuracy of your thermostat is set to ± 0.25°C. |
During test pairing, boiler control should flash confirming pair. If not, please follow Pairing Process.
When enter test pairing mode, after a 10 minute countdown the thermostat will time out.
Once the LED stops flashing, press the TEST / PAIRING button for 3 sec.
Once paired please close the boiler control panel.
You can create personalized programmes for your controller. You have the option to choose between a 5-2 days programme or a daily one by using the parameter d04 from Installer mode.
5-2 Days Programme | 24h Programme |
Weekdays | 24h |
6 sets of time/channel | 6 sets of time/channel |
Weekends | |
6 sets of time/channel | |
Total: 12 settings/week | Total: 42 settings/week |
After you have done all the changes, please press SET to confirm all your choices and to return to the Main Screen.
Press +Hr to activate the Boost function.
Press +Hr to set boost hours and then press UP or DOWN to set the boost temperature for your boost period.
The Frost protection temperature can be reviewed by pressing the UP button once, but can only be changed in Installer Mode.
Press the three buttons together simultaneously for 3 seconds.
dxx | Function | Parameter | Default value |
d01 | Temperature display increments | 0.1°C or 0.5°C | 0.5°C |
d02 | Temperature offset | +/- 3.0°C | 0.0°C |
d03 | Frost Protection setpoint temperature | 5.0°C - 17.0°C | 5.0°C |
d04 | Programmer selection | 5/2 or 24 hr (7d) | 52d |
Remove the batteries without pressing any button. Wait 2 minutes and insert the batteries again. Your device will be restarted.
When you want to change the batteries your device will use the internal memory to backup your settings.
You have 30 seconds to change the batteries before losing your settings.
SALUS Controls plc
SALUS House Dodworth Business Park South
Whinby Road, Dodworth
Barnsley S75 3SP, UK
T: +44 (0) 1226 323961
E: sales@salus-tech.com
E: techsupport@salus-tech.com
www.salus-tech.com