7 Operation
P10: This parameter delays burner activation for time as pa-
rameter value to balance temperatures of solar tank and solar
NTC sensor value (refer to section "DHW solar function").Vis-
ible only when solar NTC sensor is connected.
P11: This parameter enables or disables the DHW solar func-
tion. 1 = enabled, 0 = disabled.Visible only when solar NTC
sensor is connected.
P12: This parameter value is important for the boiler to decide
whether burner will be on or off, when DHW solar function is
active (P11=1 and solar sensor connected). Refer to "DHW
solar function" section for details. Visible only when solar
NTC sensor is connected.
P13: This parameter is functional at storage tank type models.
When storage tank is heated, boiler modulating set point is
equal to DHW-set point + this parameter value. Visible only for
storage tank type models.P14: Capacity of the pump at DHW
mode. Visible only for storage tank type models.
P15: Max temperature, that can be adjusted by left dial when
setting central heating flow temperature.
P16: This parameter is a read-only parameter which shows
the connection status of the boiler to the cloud.
P17: This parameter is related to pump capacity modulation. If
difference between flow temperature and return temperature
is below this parameter value, pump decreases its capacity
1% each 4 seconds until minimum pump capacity is reached
which is adjusted by parameter P07. If difference between
flow temperature and return temperature is above this param-
eter value, pump increases its capacity 1% each 4 seconds
until maximum pump capacity is reached, which is adjusted
by parameter P08.
P18: Burner can operate up to CH setpoint + P18 value. After
burner is off. The following conditions must occur for the next
burner operation.
- Anti-cycling time is elapsed.
- Flow temperature < CH set point -P18
P19: Min. temperature, that can be adjusted by left dial when
setting central heating flow temperature.
7.10.3.3
Entering Service Parameters (P)
Service settings menu comprises parameters that can only be
changed and adjusted by qualified service persons.
To reach service parameters, follow the instruction shown be-
low;
Servicing manual
32
a
The info menu icon
appears on the screen.
Turn left
dial
Adjust
first digit to
"7".
"P00" will appear on the
screen.
a Push
a Push
7.10.3.4
Select P00 to reach service
parameters (P).
Turn right dial to select
index number.
Push
when the parame-
ter that you want to change
appears on the screen.
Change parameter value
with right dial.
After changing parameter
value;
Push
to apply change
Push
to cancel change
D2CND028A1AA + D2CND028A4AA + D2CND035A1AA +
D2CND035A4AA + D2TND028A4AA + D2TND035A4AA
a
Spanner icon will be
displayed with "PAS" caption.
a
Adjust
second digit to "4"
and then push
a
Adjust
third digit to "2".
Wall-mounted condensing boiler
ESIE17 - 09 / 2017.11