4 Part replacement

4.4 Fan Group Removal

Fan group consists of fan,gas manifold,gas valve and silencer.
Isolate the appliance from power supply and closedown
the gas valve.
Open the appliance(refer to Section 4.2).
Disconnect the fan and gas valve wire connectors (refer
to Section 4.3).
Remove the gas supply pipe from the gas valve and
brass nipple by using wrench (1).
(1)
Servicing manual
14
Unscrew the 2xM5 screws that connect gas manifold and
burner hood (2).
Seperate the gas manifold from the burner hood clip and
take out the fan group from the burner hood (3)
Remove the silencer from the fan (4)
(4)
Undo 2xM5 screws that connect gas valve to fan using
socket wrench or screwdriver (5).
Undo 4xM6 T25 torx screw that provide fan-gas manifold
connection by using rechargeable screwdriver tool (6).
(5)
Re-assemble in reverse order.
Ensure the non-return flab mounted correctly (between
gas manifold and fan ) (7).
D2CND028A1AA + D2CND028A4AA + D2CND035A1AA +
D2CND035A4AA + D2TND028A4AA + D2TND035A4AA
(3)
(2)
(6)
(7)