Parameter settings via the service code

The parameters of the boiler controller have been configured in the factory in accordance with
the following table.
These parameters can only be changed with the service code. Take the following actions to
activate the program memory:
1.
Press the
and the
button simultaneously, until a
2.
Use the
button to enter
15
3.
Use the
button to set the parameter you wish to configure, on the service display.
4.
Use the
and
button to set the parameter to the required value (visible) on the temperature display.
5.
After all the required changes have been entered, press the
The boiler controller has now been reprogrammed.
Note
Pressing the
button will take you out of the menu without saving the parameter changes.
Example: Changing from 'combi' to 'hot water only'
1.
Press the
and the
button simultaneously.
2.
Use the
button to go to
15
3.
Press the
button 1 x. A 0 and a 1 will appear on the display.
4.
Use the
button to change the 0 to 2.
5.
Press the
button until
P
appears.
6.
The change has now been implemented. The unit will only respond to a hot water request.
Para-
meter Setting
0
Service code [15]
1
Installation type
2
CH pump continuous
3
Set maximum CH power
3.
4
Set maximum hot water power
5
Min. leaving water temperature of the fuel
line
5.
Max setting value leaving water
temperature via operating panel
6
Min. outdoor temperature of the fuel line
7
Max. outdoor temperature of the fuel line
8
CH pump post-running time after CH
operation
9
CH pump post-running time after boiler
operation
A
Setting three-way valve or shut-off valve
MIT
b
Booster
C
Step-by-step modulation
c
Minimum rpm CH
c.
Activation external power saving switch
Daikin Europe NV
appears on the service display and a
0
(service code) on the temperature display.
button until
.
EKOMB*AAV1
22
28
-
-
0
0
0
0
70
70
80
80
99
99
25
25
90
90
-7
-7
25
25
1
1
1
1
0
0
1
1
1
1
30
30
40
40
on the temperature display.
0
P
appears on the service display.
33
Description
-
Access to installers settings, the service code must be entered
(=15)
0
0= combi
1= space heating + hot water by means of storage tank
2 = hot water only
3 = space heating only
0
0= post-running pump only
1= pump continuously active
2= pump continuously active with external MIT switch
3= pump continuously active with ext. power saving switch
70
Setting reach set value parameter c up to 85%
80
Not applicable
99
Setting reach set value parameter d up to 100% (=99 + 1x )
25
Setting reach 10°C to set value parameter 5
90
Setting reach 30°C to 90°C
-7
Setting reach -9 to 10°C
25
Setting reach 15°C to 30°C
1
Setting reach 0 to 15 minutes
1
Setting reach 0 to 15 minutes
(n/a for Combi unit)
0
0= powered during CH operation
1= powered during hot water operation and rest
2= three-way valve in CH setting if device not in rest
3= zone regulation
4= External DHW tank pump
5= Powered during CH demand and rest
6= Powered during hot water operation
0
0= off
1= on
1
0= step-by-step modulation off during CH operation
1= step-by-step modulation on during CH operation
2= Power control by Open Therm room thermostat enabled
30
Settings reach 20 – 50% (40%=propane)
40
0= external power saving switch input (connector X4, pos 4-5)
41