C02: Increasing this parameter value helps ignition problems
by increasing the ignition capacity. Factory setting is "0" (zero)
and adjustment will be done as trial and error in the field. 2%
increment is recommended at each trial. Too much increasing
may cause loud ignition.
C03: This parameter is used to increase maximum allowable
flue duct length by increasing fan speed. Adjust this parameter
to "3" to use longer flue ducts for C13x and C33x types of flue
systems.
C04: Minimum capacity of the boiler can be increased with
increasing this parameter value. In case there is a problematic
combustion at minimum capacity, this parameter should be
increased to overcome the problem.
C05: This parameter is adjustable but after the adjustment,
the PCB will assign a value to this parameter, so adjusted
value will be corrected by the PCB automatically. This value
should be adjusted in case combustion is instable so, better
combustion will be initiated and PCB will assign the required
value itself afterwards.
C12: This parameter can only be adjusted after manual cali-
bration process (refer to section "Manual SCOT calibration").
If CO2 percentage is below standard limits, this parameter
value must be increased to obtain a CO2 value inside the
limits (allowable CO2 limits are given at "technical specifica-
tions").
C13: This parameter can only be adjusted after manual cali-
bration process (refer to section "Manual SCOT calibration").
If CO2 percentage is below standard limits at minimum ca-
pacity, this parameter value must be increased to obtain a
CO2 value inside the limits (allowable CO2 limits are given at
"technical specifications").
7.10.7.2
Entering SCOT Parameters
INFORMATION
Enter the password (742) as indicated in page 30.
Select the C parameters as shown below.
By tuning left dial you can
scroll through between
P,C,E parameters.
In this step, C parameters can not be changed. You can only
monitor the values of C parameters.
D2CND028A1AA + D2CND028A4AA + D2CND035A1AA +
D2CND035A4AA + D2TND028A4AA + D2TND035A4AA
Wall-mounted condensing boiler
ESIE17 - 09 / 2017.11
The parameters C00 to C05 can be adjusted by entering an-
other password. To make these parameters adjustable, follow
the steps shown below;
Select "CE"
115
Adjust first
digit to "1"
and then
Adjust
push
second digit
to "1" and
then push
115
Adjust third
digit to "5"
and then
push
Now, parameters
C00 - C05 are adjustable.
Select the parameter you
want to change and press
Change parameter value
with right dial.
After changing parameter
value;
Push
to apply change
Push
to cancel change
a Push
b Push
7 Operation
a
115
115 115
a
b
0
Servicing manual
35