E: 9A. Coil 1 (Expansion Valve 1) Error - Fujitsu ASYG07-14KGTF Service Manual

Table of Contents

Advertisement

2-39. E: 9A. Coil 1 (expansion valve 1) error

Indicator
Indoor unit
EEV coil
Detective actuator
Main PCB
Forecast of cause
Check point 1. Check the connection of EEV connector
Check if the connector is loose connection or not.
Check point 2. Check the EEV wire
Check if the wire of EEV has damage or not. (Slash, Braking of wire, Pinching, etc.)
→ If it is abnormal, replace EEV coil.
Check point 3. Check the EEV coil
Check if the circuit of EEV coil winding is good or not. (Refer to
03-89.)
→ If it is abnormal, replace EEV coil.
Check point 4. Check the output of EEV on the main PCB
Check if the DC 13 V is on between the Pin No.1 of P30, PA30, PC30, PD30 and PE30 and GND
Pin. (Disconnect the wire of EEV when you check the output of EEV.)
→ If it is abnormal, replace the main PCB.
Check point 5. Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
2-39. E: 9A. Coil 1 (expansion valve 1) error
Operation indicator
Timer indicator
Economy indicator
Error code
Coil (Expansion valve) driver circuit open detected.
End
- (03-67) -
9 time flash
10 time flash
Continuous flash
E: 9A
EEV coil loose connection
EEV wires cut or pinched
Defective EEV coil
Main PCB (DC 13 V) output abnormal
"Service parts information"
on page
2. Troubleshooting with error code