Fujitsu ASYG07-14KGTF Service Manual page 264

Table of Contents

Advertisement

2-18. E: 51. Indoor unit fan motor error (Indoor unit)
Indicator
Indoor unit
Detective actuator
Indoor unit
Forecast of cause
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
→ If fan or bearing is abnormal, replace it.
Check point 2. Check ambient temperature around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat)
→ Upon the temperature coming down, restart operation.
Check point 3. Check indoor unit fan motor
Check Indoor unit fan motor. (Refer to indoor unit fan motor in
03-89.)
→ If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Check point 4. Replace the main PCB
If Check Point 1 to 3 do not improve the symptom, replace the main PCB.
2-18. E: 51. Indoor unit fan motor error (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
Main PCB
Fan motor
End
Continuous flash
When the actual rotation number of the indoor unit fan
motor is below 1/3 of the target rotation number
continuously for more than 56 seconds.
Fan rotation failure
Fan motor winding open
Motor protection by surrounding temperature rise
Control PCB failure
Indoor unit fan motor failure
"Service parts information"
- (03-44) -
5 time flash
1 time flash
E: 51
on page
2. Troubleshooting with error code

Advertisement

Table of Contents
loading

Table of Contents