E: 99. 4-Way Valve Error (Outdoor Unit) - Fujitsu ASYG07-14KGTF Service Manual

Table of Contents

Advertisement

2-38. E: 99. 4-way valve error (Outdoor unit)

Indicator
Indoor unit
Indoor unit
Heat exchanger temperature
thermistor
Room temperature thermistor
Detective actuator
4-way valve
Forecast of cause
Check point 1. Check connection of connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
Check point 2. Check thermistor of Indoor unit
Isn't it fallen off the holder?
Is there a cable pinched?
Check characteristics of thermistor, refer to
page 03-40 and
"E: 42. Indoor unit heat exchanger sensor error (Indoor unit)"
→ If defective, replace the thermistor.
2-38. E: 99. 4-way valve error (Outdoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
main PCB
"E: 41. Room temperature sensor error (Indoor unit)"
- (03-65) -
9 time flash
9 time flash
Continuous flash
When the indoor heat exchanger temperature is
compared with the room temperature, and either
following condition is detected continuously two times,
the compressor stops.
Indoor heat exchanger temp. - Room temp. > 10°C
(Cooling or Dry operation)
Indoor heat exchanger temp. - Room temp. < -10°C
(Heating operation)
If the same operation is repeated 5 times, the
compressor stops permanently.
Connector connection failure
Thermistor failure
Coil failure
4-way valve failure
Main PCB failure
Controller PCB failure
E: 99
on
on page 03-41.
2. Troubleshooting with error code

Advertisement

Table of Contents
loading

Table of Contents