Airwell HVVA-025N-01M22 Service Manual page 34

High wall type indoor unit (n platform) hvva range r410a

Advertisement

C. One wired controller controls multiple units
0151800244B PCB
CN22
CN22-1
Note:
1. Plug the wired controller terminal to the CN22 terminal of master unit which wired address is 0.
2. The CN22-1 terminal of the previous unit is connected to the CN22 terminal of the next unit
3. Wired address setting
SW01_1
SW01_2
Wired control
SW01_3
address
SW01_4
4. One controller can Max. control 16 indoor units.
5. Hand-in-hand connection method
6. The singal line is polarity
7. The singal line diameter and length
Length of signal line (m)
≤ 250
The shielding lay of the signal line must be grounded at one end.
The total length of the signal line shall not be more than 250m.
CN22
[1]
[2]
[3]
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
...
...
...
ON
ON
ON
Wiring dimensions
2
0.75mm
×3 core shielded line
270
CN22
CN22-1
[4]
Wired control address
OFF
Master unit in group control
ON
Slave unit 1 in group control
OFF
Slave unit 2 in group control
ON
Slave unit 3 in group control
...
......
ON
Slave unit 15 in group control