WARNING: Risk
of equipment
damage.
WARNING: Risk
of equipment
damage.
WARNING: Risk
of equipment
damage.
NOTES:
NOTES:
NOTES:
Enphase IQ Cable safety
DANGER: Risk of
electric shock.
WARNING: Risk
of electric shock.
Risk of fire.
WARNING:
6
IQ8MC/IQ8AC/IQ8HC Installation and Operation Manual
Install the microinverter under the PV module to avoid direct exposure to rain,
UV, and other harmful weather events. Always install the microinverter bracket
side up. Do not mount the microinverter upside down. Do not expose the AC or
DC connectors (on the IQ Cable, PV module, or microinverter) to rain or
condensation before the connectors are mated.
The maximum open circuit voltage of the PV module must not exceed the
specified maximum input DC voltage of the Enphase microinverter. Refer to the
Enphase Compatibility Calculator
with the microinverter. Use IQ8 Series Microinverters only with compatible PV
modules as per
Enphase Compatibility
incompatible PV module voids Enphase warranty.
You must match the DC operating voltage range of the PV module with the
allowable input voltage range of the Enphase microinverter.
The Enphase microinverter is not protected from damage due to moisture
trapped in cabling systems. Never mate microinverters to cables that have been
left disconnected and exposed to wet conditions. This voids the Enphase
warranty.
The Enphase microinverter functions only with a standard, compatible PV
module with appropriate fill factor, voltage, and current ratings. Unsupported
devices include smart PV modules, fuel cells, wind or water turbines, DC
generators, non-Enphase batteries, and other devices. These devices do not
behave like standard PV modules, so operation and compliance are not
guaranteed. These devices may also damage the Enphase microinverter by
exceeding its electrical rating, making the system potentially unsafe.
The Enphase microinverter has field-adjustable voltage and frequency trip
points that may need to be set, depending upon local requirements. Only a
competent authorized installer with the permission and following requirements
of the local electrical authorities should make adjustments.
Installers must check the manufacturing date of the products to ensure that the
installation date is within one year of the manufactured date of the products.
Contact your local distributor to validate the date code.
Use a G99 approved third party network protection relay for PV systems with
system size above 17kW per phase.
Do not install the IQ Terminator while the power is connected.
When stripping the sheath from the IQ Cable, make sure the conductors are
not damaged. If the exposed conductors are damaged, the system may not
function properly.
Do not leave AC connectors on the IQ Cable uncovered for an extended
period. You must cover any unused connector with an IQ Sealing Cap.
Make sure protective IQ Sealing Caps have been installed on all unused AC
connectors. Unused AC connectors are live when the system is energized.
Use the IQ Terminator only once. If you open the IQ Terminator following
installation, the latching mechanism is destroyed. If the latching mechanism
is defective, do not use the IQ Terminator. Do not circumvent or manipulate
the latching mechanism.
When installing the IQ Cable, secure any loose cable to avoid the risk of
cable insulation abrasion against the roof surface.
© 2023 Enphase Energy Inc. All rights reserved.
to verify PV module electrical compatibility
Calculator. Using an electrically
September 2023
IOM-00029-1.0