CONTENTS Getting Other Information and Publications ..3 Heating ............. 24 Wall Mount General Information ......4 Balanced Climate Mode ........ 25 Air Conditioner Wall Mount Model Nomenclature ..4 Defrost Cycle ............. 25 Shipping Damage ..........4 Low Pressure Switch Bypass Operation ..... 26 General ...............
WALL MOUNT GENERAL INFORMATION Air Conditioner Wall Mount Model Nomenclature – MODEL SERIES CONTROL MODULES (See Spec. Sheet S3584) CAPACITY 42 – 3½ Ton COIL OPTIONS 48 – 4 Ton X – Standard 60 – 5 Ton 1 – Phenolic Coated Evaporator 2 –...
5/8". Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille Kits RG5 or RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information.
FIGURE 3 2. Locate the filter support brackets and remove the four (4) screws holding them to the top of the Removing Second Filter control panel (see Figure 6). FIGURE 6 Remove Four Screws 3. Reverse the order for new filter installation. 3.
Fresh Air Intake 6. Install the right 2" filter first followed by the left filter (see Figures 9 and 10). All units are built with fresh air inlet louvers punched NOTE: When installing new filters, make sure that in the side grilles. airflow arrows on filters point up.
Inspect wall surfaces Bard recommends at least 2' between solid objects for obstructions that could hinder unit installation and return grilles or registers. Ductwork may be used to...
5/8". It is recommended that a and return ducts must be properly sized for the design Bard Return Air Grille Kit is installed that is designed airflow requirement of the equipment. Air Conditioning specifically for the wall mount product. Contact the Contractors of America (ACCA) is an excellent guide local Bard distributor or visit www.bardhvac.com for...
• Small straight (thermostat) screwdriver 3. Position the wall mount unit close to the wall surface where it will be installed. Install rain • Tape measure flashing at the top of the unit facing the wall by • Leveling device hooking the hem bend into the rear bend of the unit top (see Figure 14).
TABLE 2 Minimum Clearances Required to Combustible Materials Model Supply Air Duct (1st 3') Cabinet W42HC W48HC 1/4" 0" W60HC FIGURE 12 Vent Installation/Removal Clearance Required OBJECT OR WALL VENTS CAN BE INSTALLED FROM EITHER SIDE OF UNIT. " 2" 45"...
FIGURE 14 Mounting Instructions SEAL WITH BEAD UNITS REQUIRED DIMESIONS OF CAULKING ALONG REQUIRED DIMESIONS TO ENTIRE LENGTH OF MAINTAIN 1/4" MIN. CLEARANCE 30 1/2 10 1/2 6 1/4 1 1/4 29 3/4 16 1 7/8 TOP. FROM COMBUSTIBLE MATERIALS W42HC-W48HC RAIN FLASHING UNITS...
FIGURE 15 Electric Heat Clearance NOTE 1: SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES. WARNING Fire hazard. Maintain minimum 1/4" clearance between the supply air duct and combustible materials in the first 3' of ducting.
FIGURE 16 Wall Mounting Instructions See Figure 14 Mounting Instructions FACTORY SUPPLIED RAIN FLASHING. WALL STRUCTURE MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR OPENING RETURN AIR OPENING WOOD OR STEEL SIDING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT. CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION SIDE VIEW...
FIGURE 18 Common Wall Mounting Installations SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN RAIN FLASHING RAFTERS FLASHING RAFTERS FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT OPENING WITH GRILLE FINISHED CEILING SURFACE RETURN AIR RETURN AIR OPENING WITH...
Wiring – Main Power All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions WARNING must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material.
DDC Connections the upper control panel where the connections are made. (The field wire shield can be removed for wire 11 terminal is filter switch, common contact on installation.) If field power is supplied to the right of auxiliary terminal strip (F Control option only) side of the unit, the low voltage wires can be run under 12 terminal is filter switch, normally open contact on the field wire shield to access the low voltage terminal...
Discharge Air Sensor During dehumidification, the indoor blower speed is reduced to help with the humidity removal. A humidity The discharge air sensor provides a temperature reading sensing thermostat or humidistat is required to control of the supply air leaving the unit. The sensor is a 10K dehumidification operation.
FIGURE 20 Thermostat Connections Completestat Model #CS9B-THOA or Model #CS9BE-THOA W1/E Thermostat W1/E YO/D Bard #8403-060 Optional CO2 Controller Bard Part #8403-067 24VAC CO2 OUT TEMP-OUT Unit Low B/W1 Voltage Term. Strip 12-Pin Vent Plug ALL VENT OPTIONS PLUG IN HERE If not equipped with a ventilation option to plug in, a jumper plug must be installed.
Thermostat Connections Units With Dehumidification 8403-038 Mechanical Humidistat T4 Pro 8403-095 T6 Pro 8403-090 or 8403-092 8403-047 Electronic Humidistat Optional CO2 Controller Bard Part #8403-067 24VAC CO2 OUT TEMP-OUT Unit Low B/W1 Voltage Term. Strip 12-Pin Vent Plug ALL VENT OPTIONS PLUG IN HERE If not equipped with a ventilation option to plug in, a jumper plug must be installed.
All W**AC wall-mounted air conditioner series models Topping Off System Charge are supplied with a remote reset for the high and low If a leak has occurred in the system, Bard pressure switch. If tripped, the pressure switch may be Manufacturing recommends reclaiming, evacuating reset by turning the thermostat off then back on again.
Service Hints However, three phase compressors will rotate in either direction depending upon phasing of the power. 1. Caution owner/operator to maintain clean air filters Since there is a 50-50 chance of connecting power at all times and also not to needlessly close off in such a way as to cause rotation in the reverse supply and return air registers.
Balanced Climate™ is a great comfort feature that can system in the defrost mode. easily be applied under any normal circumstances. If the Bard air conditioning system is being set up During the defrost mode, the refrigerant cycle switches in a typical environment where 72°F is the lowest...
In order to terminate the defrost test, the SEN JMP service technician to override or speed up this timing jumper must be removed. If left in place too long, the period and shorting out the SPEEDUP terminals for a compressor could stop due to the high pressure control few seconds can do this.
High Pressure Switch Operation The control has a built-in lockout system that allows the unit to have the high pressure switch trip up to two times in 1 hour and only encounter a “soft” lockout. A “soft” lockout shuts the compressor off and waits for the pressure switch to reset, which at that point then allows the compressor to be restarted as long as the 5-minute short cycle timer has run out.
SERVICE Solid State Heat Pump Control NOTE: If there was no power to 24 volt transformer, Troubleshooting Procedure the compressor and outdoor fan motor will not start for 5 minutes. This is because of the 1. NOTE: A thorough understanding of the defrost compressor short cycle protection.
Checking Temperature Sensor Outside 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part Unit Circuit is ± 10%.) 1. Disconnect temperature sensor from board and 4. If sensor resistance reads very low, sensor is from outdoor coil.
“Continuous Fan” only problem identified. on the “G” terminal. NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C 2. If the system is excessively noisy, does not appear contain the X13-Series Motors.
TROUBLESHOOTING GE X13-SERIES ECM2.3 ™ MOTORS CONT’D. Model SelecTech Communication Diagnostics B. If the motor has proper high voltage as identified above (If the Motor Is Not Running 2. Initiate a demand from the thermostat and check the Model X13 Communication Diagnostics The SelecTech motor is communicated through 24VAC #1), proper low voltage to a programmed voltage between the common and the appropriate motor...
Fan Blade Setting Dimensions R-410A Refrigerant Charge Shown in Figure 25 is the correct fan blade setting This unit was charged at the factory with the quantity of for proper air delivery across the outdoor coil. Refer to refrigerant listed on the serial plate. AHRI capacity and Table 10 for unit specific dimension.
TABLE 11A Cooling Pressure – Standard Airflow Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side W42HC 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side W48HC 80/67...
Page 34
TABLE 12 Cooling Pressure – Balanced Climate Airflow Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side W42HC 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side W48HC 80/67...
TABLE 13 Electrical Specifications − W**HC Series Single Circuit Multiple Circuit Maximum Minimum Rated Volts & Field External Field Power Ground Maximum Field Model Circuit Minimum Phase Power Fuse or Wire Size Wire Size External Power...
Orange Wire thermostat or other controlling device. Each speed tap w/Black Stripe is programmed by Bard at the factory to different motor torque settings (see Figure 27). Manual 2100-711F Page 36 of 45...
characteristics. See Dirty Filter Switch Adjustment Switch), begin restricting the air filter of the unit for instructions on how to make proper switch using a piece of cardboard under the filters until adjustments. the switch trips and the light comes on. If the filter is restricted by 75% (or desired restriction 3.
5. Replace the upper front panel and repeat Steps 7. Install the outer control panel cover. This 1-3. Continue to make adjustments described in completes the adjustment. Step 4 until the desired restriction is obtained. 6. Remove the restriction and reset the filter switch. Replace the switch cover once adjustment is complete.
TABLE 17 Maximum ESP of Operation Electric Heat Only Model W42HC, W48HC W60HC Outlet FRONT FRONT Speed High High -A0Z -A04 -A05 -A10 -A15 -A20 -B0Z -B05 -B06 -B09 -B15 -B18 -C0Z -C05 -C09 -C15 Values shown are for units equipped with standard 1" throwaway filter or 1"...
Need help?
Do you have a question about the W42HC-A and is the answer not in the manual?
Questions and answers