Banner R95C Series Manual

Banner R95C Series Manual

8-port discrete bimodal to io-link hub

Advertisement

Quick Links

R95C 8-Port Discrete Bimodal to IO-Link Hub
Instruction Manual
Models
Housing
R95
Overview
The R95C-8B21-KQ hub connects two discrete channels to each of the eight unique ports, providing access to monitoring and configuring those
ports with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/
Host connection.
Configuration
For more information, see P/N 227447
Input State
Table 1: Measurements – Female Pins
Port 1-Port 8 Pin Number: Description
Pin 4 – Discrete 1
Pin 2 – Discrete 2
Original Document
227446 Rev. A
• Compact bimodal to IO-Link device converter that connects discrete inputs and sends
the value to the IO-Link Master
• Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable One-
shot, ON/OFF Pulse-stretcher and Totalizer
• Measurement Metrics: Count, Events Per Minute (EPM), and Duration
• Discrete Mirroring: Discrete signals (In/Out) from all eight ports can be mirrored to any
of the eight ports, Discrete Out, or the host white wire output
• Outputs a discrete value as received from IO-Link Master Process Data Out
• Discrete input/output can be independently configured as NPN or PNP
• Rugged over-molded design meets IP65, IP67, and IP68
• Connects directly to a sensor or anywhere in-line for ease of use
• R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IO-Link
devices into an IO-Link system
Function
Converter
C
8B21
C = Converter
8B21 = 8-port,
bimodal, 2
inputs, 1 output
R95C-8B21-KQ IO-Link Data Reference Guide and P/N 227506 R95C-8B21-KQ IODD Files .
Figure 1. Logic Flow
Delay Mode
• Disabled
• On/Off Delay
Discrete 2
• On/Off/Retriggerable One-shot
Selection
• On/Off Pulse Stretcher
• Totalizer
Ouput
Mirroring
Enable
Disabled
Host
Enabled
Mirroring
Enable
IO Metric
Count Value
Duration Value
Events per Minute Value
Reset Metrics
Count Value
Duration Value
15 December 2022
Control
Connector
K
K = IO-Link
Q = M12 integral
quick disconnect
Measurement Statistics
Measurement
• Count
Statistics
• RPM
• Duration
Process Data In
Input
Process Data
• Discrete 1 and 2 Input State (active/inactive)
Input
• Selected Measurements [1]..[4]
Process Data In
Process Data
• Discrete 2 Output State (active/inactive)
Input
• Discrete 1 Input State (active/inactive)
• Selected Measurements [1]..[4]
Enabled
Mirroring - Discrete 2 Output
Mirroring
• Port/Channel selected state driven to Pin 2 (F)
Process Data
Process Data Out - Discrete 2 Output
Output
• Process Data Out selected state driven to Pin 2 (F)
Host Mirroring
Host Mirroring - Discrete Host Out
• Port/Channel selected state driven to Pin 2 (M)
Description
Running count of the received input pulses
Duration of the last input pulse in µs with 500 µs granularity
Running count of the number of pulses received averaged over one
minute
Range: 1 to 37,500
Do Not Reset
Reset
Running count of the received input pulses
Duration of the last input pulse in µs with 500 µs granularity
Q
227446

Advertisement

loading

Summary of Contents for Banner R95C Series

  • Page 1 R95C 8-Port Discrete Bimodal to IO-Link Hub Instruction Manual • Compact bimodal to IO-Link device converter that connects discrete inputs and sends the value to the IO-Link Master • Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable One- shot, ON/OFF Pulse-stretcher and Totalizer •...
  • Page 2 R95C 8-Port Discrete Bimodal to IO-Link Hub Port 1-Port 8 Pin Number: Description IO Metric Description Running count of the number of pulses received averaged over one minute Events per Minute Value Range: 1 to 37,500 • Do Not Reset Reset Metrics •...
  • Page 3: Mechanical Installation

    It can be used to automatically parameterize sensors or lights and to transmit process data. For the latest IO-Link protocol and specifications, please visit www.io-link.com. For the latest IODD files, please refer to the Banner Engineering Corp website at: www.bannerengineering.com. Mechanical Installation Install the R95C 8-Port Hub to allow access for functional checks, maintenance, and service or replacement.
  • Page 4: Specifications

    Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell) Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave) Certifications Banner Engineering Europe Park Lane, Culliganlaan 2F bus 3, 1831 Diegem, BELGIUM Turck Banner LTD Blenheim House,...
  • Page 5: Banner Engineering Corp Limited Warranty

    Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period.
  • Page 6 R95C 8-Port Discrete Bimodal to IO-Link Hub This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF...