Connecting the cRIO-9039 to the Host Computer or
Network Using Ethernet
Complete the following steps to connect the cRIO-9039 to a host computer or Ethernet
network using the RJ-45 Gigabit Ethernet port 1. NI recommends using the RJ-45 Gigabit
Ethernet port 1 for communication with deployed systems.
Note
You can configure the RJ-45 Gigabit Ethernet port 2 in Measurement &
Automation Explorer (MAX) under the Network Settings tab.
1.
Power on the host computer or Ethernet hub.
2.
Connect the RJ-45 Gigabit Ethernet port 1 on the cRIO-9039 to the host computer or
Ethernet hub using a standard Category 5 (CAT-5) or better shielded, twisted-pair
Ethernet cable.
Caution
installation, do not use a cable longer than 100 m (328 ft).
The cRIO-9039 attempts to initiate a DHCP network connection the first time you
connect using Ethernet. The cRIO-9039 connects to the network with a link-local IP
address with the form 169.254.
Finding the cRIO-9039 on the Network (DHCP)
Complete the following steps to find the cRIO-9039 on a network using DHCP.
1.
Disable secondary network interfaces on the host computer, such as a wireless access
card on a laptop.
2.
Ensure that any anti-virus and firewall software running on the host computer allows
connections to the host computer.
Note
software for information about configuring the firewall to allow communication
through the UDP 44525.
3.
Launch MAX on the host computer.
4.
Expand Remote Systems in the configuration tree and locate your system.
Tip
number, such as NI-cRIO-9039-1856AAA.
Finding the cRIO-9039 on the Network (Static IP)
Complete the following steps to find the cRIO-9039 on the network if the host computer is
using a static IP address. The following instructions are for host computers running
Windows 7. For more information about performing the network configuration steps in this
section, visit
www.microsoft.com
1.
Obtain IP settings from the host computer.
a)
Click Start»Control Panel»Network and Sharing Center.
b)
Select the primary network connection, which may appear as Local Area
Connection or something similar.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
To prevent data loss and to maintain the integrity of your Ethernet
.
if it is unable to initiate a DHCP connection.
x
x
MAX uses UDP 44525. Refer to the documentation of your firewall
MAX lists the system under the model number followed by the serial
and search for
change tcp/ip settings
NI cRIO-9039 User Manual | © National Instruments | 3
.