Mounting Requirements

Your installation must meet the following requirements for cooling and cabling clearance.
Allow 25.4 mm (1.00 in.) on all sides of the cRIO-9039 for air circulation, as shown in the
following figure.
Figure 9. cRIO-9039 Cooling Dimensions
25.4 mm (1.00 in.)
All Around
Cooling Dimensions
Allow the appropriate space in front of C Series modules for cabling clearance, as shown in
the following figure. The different connector types on C Series modules require different
cabling clearances. For a complete list of cabling clearances for C Series modules, visit
ni.com/info
and enter the Info Code
.
crioconn
Figure 10. cRIO-9039 Cabling Clearance
Cabling
Clearance
29.1 mm (1.14 in.)
Measure the ambient temperature at each side of the cRIO-9039, 63.5 mm (2.50 in.) from the
side and 38.1 mm (1.50 in.) forward from the rear of the cRIO-9039, as shown in the
following figure.