Ground the Front Door

For information on grounding the front door, see
Step 8
Replace the power supply bezel and secure it with the provided jackscrews.
For information on replacing the power supply bezel, see
Note
Install the following modules, if you had them removed from the chassis while mounting into the rack.
For more information on replacing components, see
Ground the Front Door
Note
Step 1
Install the grounding cable towards the side of the front door.
Step 2
Apply the star ring terminal end of the grounding cable to the front door. Tighten the screw to 11.5 to 15 in-lb (1.3 to 1.7
N-m) of torque to provide proper bonding.
Figure 15: Ground Cable to Chassis
Note
Fasten the ground straps on both the doors to the chassis.
Step 3
Connect the other round terminal of the grounding cable to the ground port on the cable management bracket on either
left or right side of the chassis. Use the front hole of the bracket that connects the top cover to the cable management
bracket. Tighten the M4 screw to 11.5 to 15 in-lb (1.3 to 1.7 N-m) of torque.
Step 4
Repeat Steps 1–3 to install the grounding cable to the other front door.
Step 5
Close and lock the front door.
Cisco Nexus 9804 NX-OS Mode Switch Hardware Installation Guide
26
• Fan trays
To comply with GR-1089, you have to bond the front doors to the ground port on the chassis using the ground
braid.