Midea MV6-252WV2GN1 Service Manual page 96

Commercial air conditioners
Table of Contents

Advertisement

Procedure
H0
Compressor inverter module
address setting is incorrect
Communication wire from outdoor main
PCB CN26 to inverter module CN8/CN9 is
loosen
Both LED1 and LED2 on inverter module
are off when power on
Replace the outdoor main PCB, is the
malfunction solved?
Replace the inverter module
No
2
No
3
No
No
Reset the compressor inverter module
Yes
address via dial switch S7 on inverter
module
Yes
Reconnect the communication wire
Yes
Check the power supply circuit
Yes
V6 VRF 50/60Hz
1
4
Normal
95