Midea MV6-252WV2GN1 Service Manual page 103

Commercial air conditioners
Table of Contents

Advertisement

V6 VRF 50/60Hz
L1: DC bus low voltage protection
L1 protection
The power supply is abnormal
No output from bridge rectifier
The DC bus voltage (P, N) is abnormal
Replace the inverter module
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is lower than 350V, L1
protection will be appeared.
102
Yes
No
Yes
No
Yes
1
No
Figure 6-2.6: Inverter module terminals
Check the power supply
equipment
The reactor performs well
Yes
P
No
Replace the
reactor