Midea MV6-252WV2GN1 Service Manual page 117

Commercial air conditioners
Table of Contents

Advertisement

V6 VRF 50/60Hz
2.19 P1: Discharge pipe high pressure protection
Digital display output
Description
 Discharge pipe high pressure protection. If the system has a 3-phase protector and the 3-phase protector is connected
with the high pressure switch, the system will display P1 protection when initially powered on, and P1 protection will
disappear once the system reaches a steady state.
 All units stop running.
 Error code is only displayed on the unit with the error.
Trigger / recover condition
 Trigger condition: Discharge pressure ≥ 4.4MPa.
 Recover condition: Discharge pressure ≤ 3.2MPa.
 Reset method: Resume automatically.
Possible causes
 Outdoor unit stop valves are closed.
 High pressure/Discharge temperature switch not connected properly or has malfunctioned.
 Excess refrigerant.
 System contains air or nitrogen.
 High pressure side blockage.
 Poor condenser heat exchange.
 Main PCB damaged.
Procedure
ODU stop valves are closed
High pressure/Discharge temperature
switch connection on main PCB is loose
High pressure/Discharge temperature
switch has failed
116
P1
No
1
No
2
No
Yes
Open the stop valves
Yes
Ensure the sensor is connected properly
Yes
Replace the sensor
Flowchart continued on next page ...