Midea MV6-252WV2GN1 Service Manual page 38

Commercial air conditioners
Table of Contents

Advertisement

4.3 Startup Control for Heating Operation
Table 3-4.2: Component control during startup in heating mode
Component
Inverter compressor A
Inverter compressor B
DC fan motor A
DC fan motor B
Electronic expansion valve
A
Electronic expansion valve B
Electronic expansion valve C
Four-way valve
Solenoid valve (oil balance)
Solenoid
valve
(fast
defrosting (in heating) and
unloading (in cooling))
Solenoid valve (EXV bypass)
Solenoid valve (indoor units
bypass)
Solenoid
valve
(inverter
compressor
A
vapor
injection)
Solenoid
valve
(inverter
compressor
B
vapor
injection)
Solenoid
valve
(inverter
compressor
B
pressure
balance)
Wiring
diagram
8-12HP
14-16HP
label
COMP(A)
COMP(B)
FANA
FANB
EXVA
EXVB
EXVC
ST1
SV4
SV5
SV6
SV7
SV8A
SV8B
SV9
18-28HP
30-32HP
Controlled
operating frequency increased by 1 step / sec
Open once the four-way valve has opened,
controlled
temperature and load requirement
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge superheat
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to temperature
different between plate heat exchanger inlet and
outlet
On
Closed for 200 secs, open for 600 secs, then closed
Open for 4 mins, then closed
Off
Controlled according to load requirement
Controlled according to inverter compressor A
Controlled according to inverter compressor B
Open before compressor B startup
V6 VRF 50/60Hz
Control functions and states
according
to
load
requirement,
according
to
outdoor
ambient
37