L2: DC bus high voltage protection
L2 protection
The power supply is abnormal
No
The DC bus voltage (P, N)is abnormal
Note:
1.
The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
Yes
Check the power supply equipment
Yes
1
Replace the inverter module
Figure 6-2.7: Inverter module terminals