Wolf CWL-2-325 Installation And Operating Instructions Manual page 34

Table of Contents

Advertisement

Electrical diagram
1 = Basic pcb UWA2-B
2 = Multiple switch (option)
3 = Humidity sensor (option)
4 = USB connector
5 = USB stick for updating software (not supplied with appliance)
6 = Service connector
7 = Laptop with installed service tool (not supplied)
8 = Touchscreen on appliance
9 = Valve motor bypass valve
10 = Air temperature sensor
11 = Exhaust fan*
12 = Internal preheater incl. maximum security
13 = Supply fan*
14 = Power supply 230V 50Hz
15 = BM-2 (option)
16 = CO
sensor eBus (option)
2
17 = Heater eBus (option)
18 = Plus pcb UWA2-E (option)
19 = Connection on ModBus system (option)
20 = X12 is Jumper terminating resistance (120 W) ModBus (remove
if terminating resistance has already been placed in ModBus
system).
With Modbus application remove the jumpers X121 & X122;
when using Bus place the jumpers X12, X121 & X122; remove
Jumper X07 from Plus pcb UWA2-E when a Plus pcb is applied.
* The control cables of the fans can be switched with no problem;
when the power is switched on the appliance determines itself
which is the supply and exhaust fan!
When the appliance detects another fan (for example when a
fan is replaced during service activities), then a "wizard" starts
up automatically; follow the instructions on the display for the
correct connection of the fan cables.
34 | WOLF GmbH
Basic pcb UWA2-B
X15 = Bus/ModBus
X16 = 24V
x17 = eBus
X18 = 24V (max 5VA)
X19 = Signal output
Plus pcb UWA2-E
X03 = 24V
X04 = Bus
X06 = ModBus
X08 = Contact input 1
X09 = Contact input 2
X10 = Relais output 1
X11 = Relais output 2
X12 = Analoog input (0 to 10 V)
X13 = Analoog input (0 to 10 V)
X14 = Analoog output (0 or 10 V)
X15 = Analoog output 2 (0 or 10 V)
X16 = NTC 10K
X17 = LAN
Wire colours
C1
=
brown
C2
=
blue
C3
=
green/yellow
C5
=
white
C8
=
grey
C10
=
yellow
C11
=
green
C17
=
purple
xxxx
7100832_202010