Connecting The Condensate Discharge - Wolf CWL-2-325 Installation And Operating Instructions Manual

Table of Contents

Advertisement

Installation
5.3

Connecting the condensate discharge

The condensate discharge line for the CWL appliance is located in the lower panel. The condensate is
discharged through the drainpipe.
The siphon (with built-in aerator) is supplied separately with the appliance and must be fitted by the
installer below the appliance (bayonet connection). The siphon has an external connection diameter of 32
mm. The siphon is connected to the inner sewer system. It is recommended to fit an odor trap between
the sewer system and siphon in order to avoid unpleasant odors.
Warning
Never switch the two condensate discharge connections below the appliance,
It is recommended to use a 32 mm connection with gasket (HT DN32) (not supplied with the
appliance) so that the siphon can be cleaned easily in the future.
Warning
Important: During assembly always apply a lubricant, such as acid-free vaseline, to the
rubber sealing ring in the gasket. This gasket connection has to be disconnected when
servicing the appliance! The siphon must not be glued to the condensate discharge line.
The condensate discharge can be connected, for example, with a straight or angled connection with
gasket. Slide the condensate discharge connection with gasket with sufficient length across the
connection of the siphon.
A = CWL -2-325 right-hand version
B = Fitting siphon below in CWL appliance
C = Examples with condensate discharge connections with gasket HT DN32
D = Detachable connection
E = Example of odor trap
7100832_202010
xxxx
WOLF GmbH | 13