THE BUZZER
SOUNDS
CONTINUOUSLY
AND THE DISPLAY
SHOWS ONE OF THE
FOLLOWING CODES:
A80E, A810, F808
THE DISPLAY
SHOWS THE
FOLLOW CODE:
A60D
THE BUZZER
SOUNDS
CONTINUOUSLY
AND THE DISPLAY
SHOWS ONE OF THE
FOLLOWING CODES:
A004 F004
THE BUZZER
SOUNDS
CONTINUOUSLY
AND THE DISPLAY
SHOWS ONE OF THE
FOLLOWING CODES:
F805
THE BUZZER
SOUNDS
CONTINUOUSLY
AND THE DISPLAY
SHOWS ONE OF THE
FOLLOWING CODES:
F704,
F70D,F70C,F302,
F303,F305,F300,F301
,F304, F002
THE DISPLAY
SHOWS THE CODE:
A900
Reduce the load to within the
threshold of 100% (or user
THE LOAD
threshold in the case of code
APPLIED TO THE
A80E).
UPS IS TOO HIGH
If the display shows an Fault:
remove the load and switch the
UPS off and back on again.
BATTERIES
MISSING OR
Check that the Battery Box is
BATTERY BOX
inserted and connected to the UPS
MISSING OR NOT
correctly.
CONNECTED
THE
Check that the temperature of the
TEMPERATURE
environment in which the UPS is
INSIDE THE UPS IS
located does not exceed 40°C.
TOO HIGH
THERE IS A FAULT
Disconnect all the utilities, switch
ON ONE OR MORE
the UPS off and back on again,
OF THE LOADS
reconnect the utilities one at a time
POWERED BY THE
to identify which one is faulty.
UPS
If possible, disconnect the power
to the load, switch the UPS off and
THE UPS IS
back on again; if the problem
MALFUNCTIONING
occurs again, call the support
centre.
THE
To take the UPS out of the
MAINTENANCE
maintenance bypass function,
BYPASS FUNCTION
open the manual bypass switch on
IS ACTIVE
the back of the UPS.
33