R.E.P.O.
a - The REPO connection (between terminal 5 and 6) is normally open.
For more information please refer to the REPO section of this
manual
6. Tighten the terminals well, close the backpanel cover and secure it with
the screws taken out earlier.
The suggested tighten force is 1.2~1.6Nm.
Combo version
Single-phase connection
4. (SINGLE-PHASE CONNECTION 9E10KI, 9E10KIXL): use 3 cables of
cross-section 10 mm
of cross-section 10 mm
(SINGLE-PHASE CONNECTION 9E15KI, 9E15KIXL): use 3 cables of
cross-section 16 mm
of cross-section 16 mm
(SINGLE-PHASE CONNECTION 9E20KI, 9E20KIXL): use 3 cables of
cross-section 25 mm
of cross-section 25 mm
Fig.3-4 6K terminal view
2
(EARTH, N and L) for the input, and 3 cables
2
for the output(EARTH, N and L).
2
(EARTH, N and L) for the input, and 3 cables
2
for the output(EARTH, N and L).
2
(EARTH, N and L) for the input, and 3 cables
2
for the output(EARTH, N and L).