Fig.3-6 10~20K three phase input terminal view
3. Tighten the terminals well, close the backpanel cover and secure it with
the screws taken out earlier.
For 10 to 15kVA the suggested tighten force is 1.2~1.6Nm. For 20kVA,
the suggested tighten force is 2.5~3 Nm.
R.E.P.O.
The terminal block on the back of the UPS also implements the R.E.P.O.
(Remote Emergency Power Off) function that can be used to shut off the
UPS remotely in case of an emergency.
For installation, connect to the device's normally open contact .
In case of an emergency, if the stop device is used, the REPO control is
closed and the UPS goes into stand-by mode and the load is completely
disconnected.
Attention: before restarting the UPS, reset the stop device.
The circuitry of the remote control terminal board is self-powered with
SELV circuits. Therefore, an external voltage supply is not required. When
a contact is closed, a maximum current of 15mA circulates.
All connections with the remote control terminal board are made through a
cable which guarantees a double insulation connection.
If you would like to bring the R.E.P.O. control outside, unscrew the two
screws securing the lower part of the backpanel cover and remove it (as
indicated in the section "Connections"). Then, proceed as follows: