EDR-8010 Series Quick Installation Guide Moxa Industrial Secure Router Version 1.1, August 2023 Technical Support Contact Information www.moxa.com/support 2023 Moxa Inc. All rights reserved. P/N: 1802080100011 *1802080100011*...
Package Checklist The EDR-8010 Series secure router is shipped with the items listed below. If any of these items are missing or damaged, please contact your customer service representative for assistance. • 1 Industrial secure router • 1 USB-C-to-DB9 cable •...
Page 3
Panel Views of EDR-8010 Series EDR-8010 Series Front Panel Front Panel: 1. USB port for ABC-02-USB 2. 1G SFP port speed LED indicator 3. 1G SFP ports 4. 1G SFP port speed LED indicator 5. 100 Mbps copper port speed LED indicator 6.
DIN-rail Mounting (DNV-certified) In the package, the metal DIN-rail mounting kit is fixed to the back panel of the EDR-8010 Series with four screws (M3 x 6 mm). Mount the EDR-8010 Series on a corrosion-free mounting rail that adheres to the EN 60715 standard.
8010 Series on the wall, as shown in the following illustrations. STEP 1: Remove the aluminum DIN-rail attachment plate from the rear panel of the EDR-8010 Series, and then attach both the wall-mounting plates with four screws (M3 x 5 mm).
STEP 2: Mounting the EDR-8010 Series on the wall requires four screws. Use the EDR-8010 Series with the wall mount plates attached as a guide to mark the correct location of the four screws. The head of the screws should be less than 7.0 mm in diameter, and the shaft should be less than 3.5 mm in diameter.
Page 8
ATTENTION Safety First! Be sure to disconnect the power cord before installing and/or wiring your EDR-8010 Series. Calculate the maximum possible current in each power wire and common wire. Observe all electrical codes dictating the maximum current allowable for each wire size.
Wiring the Redundant Power Inputs The EDR-8010 Series has two sets of power inputs—power input 1 and power input 2. The top and side views of the terminal block connector are shown below. The input terminal block (TB1) should be installed using 16-24 AWG wires.
NOTE DO NOT power off the device when loading default settings. LED Indicators The front panel of the EDR-8010 Series has several LED indicators. The function of each LED is described in the following table: - 10 -...
The EDR-8010 is not set as the Master of this Turbo Ring or is set as a Member of the Turbo Chain. The EDR-8010 Series’ coupling function is enabled to form a backup path, or the device is set as the Tail of the Turbo Chain.
Page 12
Input Voltage 12/24/48 VDC, dual power input DNV-certified for 24 VDC Power Consumption 6.36 W (max.) Operating Temperature Standard models: -10 to 60°C (14 to 140°F) Wide-temp. models: -40 to 75°C (-40 to 167°F) DNV-certified for -25 to 70°C (-13 to 158°F) Storage Temperature -40 to 85°C (-40 to 185°F) Compass Safety Distance 400 mm...