Unigas HRX92R-FGR EA Manual Of Installation - Use - Maintenance page 54

Gas - light oil burners
Hide thumbs Also See for HRX92R-FGR EA:
Table of Contents

Advertisement

PART IV: MAINTENANCE
Adjusting the gas valves group and removing the filter
MULTIBLOC DUNGS MB-DLE 405..412
Check the filter at least once a year!
Change the filter if the pressure difference between pressure connection 1 and 3 (Fig. 1-Fig. 3)is p > 10
mbar.
Change the filter if the pressure difference between pressure connection 1 and 3 (Fig. 1-Fig. 3) is twice as high
compared to the last check.
You can change the filter without removing the fitting.
1
Interrupt the gas supply closing the on-off valve.
2
Remove screws 1 ÷ 4 using the Allen key n. 3 and remove filter cover 5 in Fig. 5.
3
Remove the filter 6 and replace with a new one.
4
Replace filter cover 5 and tighten screws 1 ÷ 4 without using any force and fasten.
5
Perform leakage and functional test, p
6
Pay attention that dirt does not fall inside the valve.
6
5
3 4
DUNGS MB-DLE 415 - 420 B01 1" 1/2 - 2"
Check the filter at least once a year!
Change the filter if the pressure difference between pressure connection 1 and 2 (Fig. 1-Fig. 2) p> 10 mbar.
Change the filter if the pressure difference between pressure connection 1 and 2 (Fig. 1-Fig. 2) is twice as high
compared to the last check.
You can change the filter without removing the fitting.
1
Interrupt the gas supply closing the on-off valve.
2
Remove screws 1 ÷ 6 (Fig. 3).
3
Change filter insert.
4
Re-insert filter housing, screw in screws 1 ÷ 6 without using any force and fasten.
5
Perform leakage and functional test, p
6
Pay attention that dirt does not fall inside the valve.
5
4
2
3
= 360 mbar.
max.
2
1
0
Fig. 34
4
3
5
= 360 mbar.
max.
0
1
Fig. 37
6
5
D
3
2
4
A
A
54
Fig. 35
1
2
Fig. 36
5
3
6
4
Fig. 38
E
E
Fig. 39
D
C
B
C
B

Advertisement

Table of Contents
loading

Table of Contents