Unigas HRX92R-FGR EA Manual Of Installation - Use - Maintenance page 35

Gas - light oil burners
Hide thumbs Also See for HRX92R-FGR EA:
Table of Contents

Advertisement

The display will show these data:
Setting menu
The setting menu is divided into different blocks:
Bloc.
100
Informazioni generali
200
Controllo bruciatore
400
Curve rapporto
500
Controllo rapporto
600
Servocomandi
700
Storico errori
900
Dati di processo
The accesses to the various blocks are allowed by passwords. Passwords are divided into three levels:
User level (info): no password needed
Service level (Service)
Manifacturer level (OEM)
PHASES LIST
During operation, the following program phases are shown. The meaning for each phase is quoted in the table below
Fase /
Phase
Ph00
Fase blocco
Ph01
Fase di sicurezza
Ph10
t10 = tempo raggiungimento posizione riposo
Ph12
Pausa
t22 = tempo di salita ventilatore (motore ventilatore = ON, valvola intercetta-
Ph22
zione di sicurezza = ON)
Ph24
Verso posizione preventilazione
Ph30
t1 = tempo preventilazione
Ph36
Verso posizione accensione
Ph38
t3 = tempo preaccensione
Lock+unlock codes
Open valves
Ignition transformers energised
Fan motor energised
Oil pre-heater energised
Plant heat request
Parametere setting mode
Service mode
Closing actuator
Opening actuator
Unit measure
Descrizione
Funzione
Flame
Info mode
Description
General
Burner control
Ratio curves
Ratio control
Actuators
Error history
Process data
35
PART III: OPERATION
Password
OEM / Service / Info
OEM / Service
OEM / Service
OEM / Service
OEM / Service
OEM / Service / Info
OEM / Service / Info
Function
Lockout phase
Safety phase
t10 = home run
Standby (stationary)
t22 = fan ramp up time (fan motor = ON,
safety shutoff valve = ON)
Traveling to the prepurge position
t1 = prepurge time
Traveling to the ignition position
t3 = preignition time

Advertisement

Table of Contents
loading