In order to prevent reflections on the RS485 connection, it is absolutely
necessary to terminate the connection at the pyrometer and at the con-
verter. The termination is integrated in the pyrometer and is active when
delivered from the factory.
Moreover, use a converter with galvanic isolation (e.g. W&T 38211) to
avoid problems with ground loops.
Caution !
If the supply voltage or current output are conducted via this ca-
ble, then make sure to consider the voltage drop if the cable
length is greater than 100 m.
Disconnect the pyrometer from any voltage source
Install all required electric connections
Connect the converter with the PC
Install the converter according to instructions.
Connect the voltage supply for the pyrometer
Change the parameter
Start a terminal program such as Hyperterminal
. to
TERM
R485
42
Operating Manual MPA