2-INSTALLATION INSTRUCTIONS
CONNECTION TO FLUE
The connection between the flue and the appliance must be via a smoke duct that conforms with EN 1856-2. The connecting section
must extend no more than 4 m horizontally, with a maximum incline of 3% and containing a maximum of 3 90% bends (accessible for
inspection - do not count the T joint at the appliance outlet).
The diameter of the smoke duct must be equal to or greater than that of the outlet of the appliance (Ø 100 mm).
TYPE OF DEVICE
Minimum vertical length
Maximum length
(with 1 accessible 90° bend)
Maximum length
(with 3 accessible 90° bends)
Maximum number of accessible 90° bends
Horizontal sections
(minimum incline 3%)
Use smoke ducts with a diameter
the appliance (min. T200 class P1). The use of flexible metal tubes in fibre cement or aluminium is prohibited. For direction
changes, we always recommend the use of a T joint with an inspection cap allowing easy access for cleaning the tubes. Always
ensure that the inspection cap is replaced and hermetically sealed with the seal in tact after cleaning.
It is prohibited to connect more than one appliance to the same smoke duct, or the discharge from overhead cowling. It is prohibited to
extract the products of combustion directly through the wall, whether into indoor spaces or outdoors.
The smoke duct must be a minimum distance of 400 mm from flammable or heat-sensitive structures.
Technical Dept. - All rights reserved - Reproduction is prohibited
100mm and silicone gaskets or similar gaskets that can withstand the high operating temperatures of
SMOKE DUCT
1.5 metres
6.5 metres
4.5 metres
3
4 metres
15