<RBC-ASCU11 >
Clearing a check code of the outdoor unit
Clear the currently detected outdoor unit for each refrigerant line to which the indoor unit
controlled by the remote controller is connected. (The indoor unit check code is not cleared.)
Use the service monitoring function of the remote controller.
1
3
1
Push the [menu] button for over 10 seconds.
2
Every pushing [
displayed successively.
3
Push the [OFF timer] button to confirm the selected indoor unit.
4
Every pushing [
5
The display in A of the following figure counts down as follows at 5-second intervals:
0005
0005
0005
0005
0005
0004
0004
0004
0004
0004
"
"
"
The check code is cleared when "
However, the display counts down from "
6
After you have finished checking, push the [ON/OFF] button to return to normal mode.
Clearing a check code of the indoor unit
Push the ON / OFF button on the remote controller.
(Only the check code of the indoor unit controlled by the remote controller will be cleared.)
NOTE:
The LED on the P.C. board of the selected hot water module flashes. The hot water module for change
settings can be confirmed.
2, 4
6
or
] buttons, the indoor unit numbers in group control are
or
] buttons to set CODE No. to "F"
0003
0003
0003
0003
0003
0002
0002
0002
0002
0002
"
"
"
"
000
1,2
Indoor unit
number
4
Data
0001
0001
0001
0001
0001
0000
0000
0000
0000
0000
"
"
"
"
" appears.
005
" again.
– 38 –
"Monitoring function"