Check Codes Displayed On Remote Controller And Smms Series Outdoor Unit (7-Segment Display On I/F Board) And Locations To Be Checked - Toshiba MMU-UP0091HP-E Service Manual

Air conditioner (multi type)
Hide thumbs Also See for MMU-UP0091HP-E:
Table of Contents

Advertisement

9-4. Check Codes Displayed on Remote Controller and SMMS
series Outdoor Unit (7-Segment Display on I/F Board) and
Locations to Be Checked
For other types of outdoor units, refer to their own service manuals.
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
E01
E02
E03
E04
No. of indoor
units from
which signal is
received
normally
E06
E04
Location
Description
System status
of
detection
Remote
Indoor-remote
Stop of
controller
controller
corresponding
communication
unit
trouble
(detected at
remote
controller end)
Remote
Remote
Stop of
controller
controller
corresponding
transmission
unit
trouble
Indoor unit
Indoor-remote
Stop of
controller
corresponding
communication
unit
trouble
(detected at
indoor end)
Indoor unit
Indoor-outdoor
Stop of
communication
corresponding
circuit trouble
unit
(detected at
indoor end)
I/F
Dropping out of
All stop
indoor unit
Indoor unit
Indoor-outdoor
Only specified
communication
indoor units stop
circuit trouble
- 136 -
Check code detection
Check items (locations)
condition(s)
Communication between
• Check remote controller
indoor P.C. board and
inter-unit tie cable (A/B).
remote controller is
• Check for broken wire or
disrupted.
connector bad contact.
• Check indoor power
supply.
• Check for failure in indoor
P.C. board.
• Check remote controller
address settings
(when two remote
controllers are in use).
• Check remote controller
P.C. board.
Signal cannot be transmitted
• Check internal
from remote controller to
transmission circuit of
indoor unit.
remote controller.
--- Replace remote
controller as necessary.
There is no communication
• Check remote controller
from remote controller
and network adaptor
(including wireless) or
wiring.
network adaptor.
Indoor unit is not receiving
• Check order in which
signal from outdoor unit.
power was turned on for
indoor and outdoor units.
• Check indoor address
setting.
• Check indoor-outdoor tie
cable.
• Check outdoor terminator
resistor setting (SW100,
Bit 2).
Condition 1
• Check power supply to
All indoor unit initially
indoor unit.
communicating normally
(Is power turned on?)
fails to return signal for
• Check connection of
specified length of time.
indoor-outdoor
communication cable.
Condition 2
• Check connection of
Outdoor I / F board
communication connectors
on indoor P.C. board.
SW103, Bit4 : OFF
(Factory default)
• Check connection of
communication connectors
on outdoor P.C. board.
• Check for failure in indoor
P.C. board.
• Check for failure in outdoor
P.C. board (I/F).
Condition 1
• Check power supply to
Indoor unit initially
indoor unit.
communicating
(Is power turned on?)
normally fails to return
• Check indoor-outdoor
power-on sequence.
signal for specified
length of time.
• Check indoor address
setting
• Check wiring of Indoor-
outdoor communication
wires
• Check outdoor terminator
resistor setting (SW100,
Bit 2).