SECTION 1 - JLG SMART SYSTEM ™ ANALYZER KIT INSTRUCTIONS (1600258 CONTROLLER).
Table 1-4. Machine Configuration Programming Information (Machines equipped with 1600258 controller)
Configuration Digit
4
(DECK EXT. LIMIT
SWITCH)
5
(FUNCTION CUTOUT)
6
(GROUND ALARM)
7
(DRIVE CUTOUT)
8
(ARM GUARDS CUTOUT
OR PLATFORM DESCENT
DELAY SYSTEM)
3120442
Number
0
Deck extension limit switch not installed. (Option Number 2 must be used if there is a
power deck installed.)
1
Cuts out LIFT DOWN when deck is extended. This digit is used with roll out decks that
require a deck extension cutout. Sounds platform alarm for one second on, one sec-
ond off, one second on, and three seconds off while operator tries to perform the func-
tion that has been cut out (provided the platform alarm has been installed).
2
Cuts out HIGH DRIVE when deck is extended and below elevation. Cuts out DRIVE
when deck is extended and above elevation. This digit is used with a power deck.
Sounds platform alarm for one second on, one second off, one second on, and three
seconds off while operator tries to perform the function that has been cut out and dur-
ing the LIFT DOWN function (provided the platform alarm has been installed).
0
No function cutout installed.
1
Overload switch for French machines. — Cuts out all functions. Sounds platform
alarm for two seconds on, two seconds off, while operator tries to perform the function
that has been cut out (provided the platform alarm is installed).
2
Overload switch for Japanese machines. — Cuts out LIFT UP and DRIVE. Sounds
platform alarm for two seconds on, two seconds off, while operator tries to perform the
function that has been cut out (provided the platform alarm is installed).
0
No ground alarm installed.
1
Descent alarm. — Sounds when LIFT DOWN is active.
2
Travel alarm. — Sounds when DRIVE function is active.
3
Motion alarm. — Sounds whenever the DRIVE, LIFT or DECK function is active.
0
No drive cutout switch installed.
1
Cuts out DRIVE when deck is elevated above a predetermined elevation (varies with
machine model).
0
No arm guards cutout.
1
European (CE Specification) machines — allows LIFT DOWN until the deck is low-
ered to approximately two meters. Here it will cut out LIFT DOWN and sound the plat-
form alarm for 1/2 second on, 1/2 second off, and repeat this for three seconds. After
three seconds, the operator must re-select the LIFT function and continue to operate
LIFT DOWN. If the wires to the limit switch used to detect the deck height are cut or the
switch has failed, the platform alarm will sound as mentioned. The operator can re-
select the LIFT function and then LIFT DOWN for ten seconds, at which time it will cut
out again and the process must be repeated. NOTE: The alarm and cutout will be acti-
vated if the platform is above 2 meters, unless they have been activated in the previ-
ous ten seconds.
Description
– JLG Sizzor –
Default Setting
Before
Programming
0
0
0
0
0
1-9