1000
Vent Type
None, ERV/HRV, Passive. Fresh Air Damper
None: The thermostat does not control ventilation.
ERV/HRV: The thermostat controls an Energy Recovery Ventilator or Heat Recovery Ventilator for ventila
tion.
Passive (Fan Only): The thermostat turns on the fan for ventilation. When set to passive fan. the thermo
stat does not control a damper or ventilator. The passive ventilation/passive fan setting only runs the indoor
blov/er fan. This setting does not open a damper or run a ventilator. To use this setting for ventilation, the home
would need to be set-up with a pipe from outdoors into the return duct that is either permanently open or has a
damper that automatically opens whenever the blower fan is on.
Note: Some models only offer the passive fan setting.
1005
Vent Method
ASHRAE 2010, ASHR AE 2013. Percent On Time
Note: Options of this ISU may vary depending on the model of the thermostat.
1006
Vent Fan Control
Thermostat, Equipment
Thermostat: The thermostat turns on the ventilation and the fan when ventilation |s needed.
Equipment: Ventilation equipment controls the blower fan.
1007
Bedrooms
1-6(2)
This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1008
Home Size
1000 - 5000 Sq. Ft. (1000 Sq. Ft.)
This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1009
Vent Rate
30 - 350CFM (in 5CFM increments) (150CFM)
This ISU is only displayed v/hen ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1011
Vent Percent On Time
10%-100% (30%)
The thermostat operates ventilation equipment based on a percentage entered in the installer setup (ISU
1012). For example, if Percent on Time is set to 50%. the ventilation equipment will run at random times dur
ing a 1 hour period until it reaches a 50% run time (approximately 30 minutes). This ISU is only displayed if
ISU 1005 is set to Percent On Time.
1012
Vent Priority
Lockouts, ASHRAE
Lockouts are Priority: The thermostat places a priority on lockouts versus the ASHRAE ventilation
standard. The thermostat will not run ventilation during the following lockout conditions (if configured), unless
you manually call for ventilation:
Lockout Ventilation during Outdoor Conditions (ISU 1013. lOlA and 1015).
Lockout Ventilation during "Sleep" program periods. Note: This option is set by the user on the Ventilation
screen in the Menu.
ASHRAE Is Priority: ASHRAE requires additional ventilation following a long off cycle. The thermostat
meets the ASHRAE ventilation standard by running additional ventilation when outdoor conditions are favor
able. If ASHRAE cannot be met when outdoor conditions are favorable, the thermostat will override the outdoor
lockouts and run ventilation. When using this option, it is recommended that you increase the rate (CFM) of
the ventilation equipment to meet the ASHRAE ventilation standard in a shorter run time. The ability to lockout
ventilation during the "Sleep" is not an option when you select ASHRAE is Priority.
1013
Low Outdoor Temp
Vent Lockout
Off, -20 °F to -AO °F (in 5 °F increments) or
-28.0 °C to -A.O °C (in 2.0 °C increments)
ISU 130 must be set to Wired or Internet. This ISU is only displayed when ISU 1000 Ventilation Type is set to
ERV / HRV or Fresh Air Damper.
lOlA
High Outdoor Temp
Vent Lockout
Off, 80 °F to 110 °F (in 5 "F increments) or
26 °C to AA °C (in 2 °C increments)
ISU 130 must be set to Wired or Internet. This ISU is only displayed when ISU 1000 Ventilation Type is set to
ERV / HRV or Fresh Air Damper.
1015
High Outdoor
DewpointVent
Lockout
Off, 65 °F to 85 °F (in 5 "F increments) or
18 "C to 30 °C (in 2 °C increments)
ISU 130 must be set to Internet. This ISU is only displayed if ISU 1000 Ventilation Type is set to ERV/ HRV or
Fresh Air Damper.