Honeywell Home Lyric T6 Pro Wi-Fi Professional Install Manual page 14

Hide thumbs Also See for Lyric T6 Pro Wi-Fi:
Table of Contents

Advertisement

#ISU
ISU Name
ISU Options (defaults in bold)
Notes
391
Ext Fan RunTime
In Heat
Off. 30.60.90 seconds
2.3.4.5.6.7.8.9.10.11.12.13.14.15 minutes
After the call for heating ends, the thermostat keeps the fan on for the selected amount of time for increased
efficiency. This ISU is displayed if ISU 230 is set to Thermostat Controls Fan.
425
Adaptive Recovery
On, Off
Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier,
ensuring the indoor temperature will match the setpoint at the scheduled time.
429
Max Cool Temperature
from Min. Cool Temp, to 99 °F or to 37.0 °C (90 °F or 32 "C) The user cannot set the cooling temperature above this level.
430
Min Cool Temperature
from 50 °F or 10.0 °C to Max. Cool Temp. (50 °F or 10 °C) The user cannot set the cooling temperature below this level.
431
Max Heat Temperature
from Min. Heal Temp, to 90 "F or to 32.0 "C (90 " F or 32 "C) The user cannot set the heating temperature above this level.
432
Min Heat Temperature
from 40 °F or 4.4 °C to Max. Heat Temp. (50 °F or 10 °C)
The user cannot set the heating temperature below this level.
500
Indoor Sensor
Yes. No
Set this ISU when you want to wire a remote indoor sensor to the "S" terminals on the UWP - see 'Wiring' on
page 5. This ISU is only displayed only if ISU 130 is set to NO wired outdoor sensor configured
515
Sensor type
10k, 20k
Choose resistance type of wired indoor sensor. This ISU is only displayed when indoor sensor is configured -
ISU 500.
520
Temperature Control
Tfiermostat. Wired. Average
This ISU is only displayed when indoor sensor is configured - ISU 500. You can choose what temperature
source to be used or you can ask thermostat to use both thermostat and remote sensors for higher accuracy of
measurement.
702
Air Filters
0-2
This ISU refers to the number of air filters in the system.
711
Air Filter 1 Reminder
Off
10.20.30.45.60.90.120.150 Run Time Days
30.45.60.75 Days
3.4.5.6.9.12.15Monttis
Choose either calendar or equipment run time-based reminder.
712
Air Filter 2 Reminder
Off
10.20.30.45.60.90.120.150 Run Time Days
30.45.60.75 Days
3.4.5.6.9.12.15 Months
Choose either calendar or equipment run time-based reminder.
810
Hum Pad Reminder
Off
6.12 Calendar Months
921
Dehum Filter
Reminder
Off
30.60 Calendar Days
3-12 Calendar Months (in 1 month increments)