Figure 4 - Connection diagram
(unvented system)
Installation should be carried out
generally as shown on the following
diagram. See figure 4.
'Lochinvar Ltd.' are tested to a maximum
pressure of 12 bar and a maximum
working pressure of 8 bar.
2.1.3

Gas connection

The gas supply to this appliance must
be installed in accordance with BS 6891
(1988).
Fit the ½" gas supply cock supplied with
this unit immediately before the gas
control block. No heat or soldered joints
should be applied in the vicinity of the
gas control block, as they could cause
damage to the control.
12
1) Manual gas valve
2) Stop valve
3) Expansion vessel
4) T&P safety valve
5) Non return valve
6) Circulation pump
7) Drain valve
8) Pressure reducing valve
9) Expansion valve
A) Gas supply
B) Hot water outlet
C) Cold water supply
D) Hot water draw off points
E) Return circulation loop
IMD 0581
All connections and joints should be
tested for gas soundness with a suitable
leak detector (do not use a naked flame).
2.1.4

Flue system

The water heater should be fitted with
a flue system connected to the draught
diverter. The flue pipe should rise for
at least 50 cm. vertically before the
inclusion of any bends. If a horizontal
run of flue is required this should be
kept to the minimum length possible and
incorporate a rise of 6 cm. per metre
of run. A split clip or flange should be
provided in the flue close to the draught
diverter for ease of servicing.