Lochinvar EFW 85 Installation, Commissioning, User And Maintenance Instructions page 81

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

#
Burner state
0
INIT
1
RESET
2
STANDBY
3
PRE_PURGE_0
4
PRE_PURGE_1
5
PRE_IGNIT
6
IGNIT
7
FLAME_PROVING
8
BURN
9
POST_BURN
10
POST_PURGE_0
11
POST_PURGE_1
12
ERROR_CHECK
13
ALARM
14
BURNER_BOOT
During the ignition cycle multiple safety checks are active
False flame detection
If flame is detected at the end of the pre-spark period (Pre_Ignit) a lockout error will occur.
Re-ignition
If at the end of the safety period no flame is detected the control will go to Post_Purge to
remove any unburned gas. After this a re-ignition attempt is started following the same
cycle.
The number of re-ignition attempts is limited to Max_Ignit_Trials after which a lockout oc-
Sparking stops in the Flame_Proving state to allow for ionization detection. The
Flame establishing
curs.
time
Flame_Proving state takes Safety_Period - Ignit_Period.
Flame out too late
If at the end of the Post_Purge 0 state the flame is still detected a lockout follows.
When a flame is lost during a burn cycle the control will restart the burner. The number of
Flame loss
restarts is limited by the Max_Flame_Trials setting.
The fan speed is continuously monitored.
Fan supervision
The following conditions for the fan speed are checked:
Actions
Controller initialization
Software reset (and initialization)
Standby (waiting for demand)
Fan is not running
When an APS is enabled the APS position is checked
Fan starts at ignition speed
When an APS is enabled the APS position is checked
Fan stays at ignition speed
Igniter is started
When a LPG tank is selected, the tank valve is opened
Fan stays at ignition speed
The gas valve is opened
Igniter stays on
When a LPG tank is selected, the tank valve stays opened
Fan stays at ignition speed
The gas valve stays opened
The igniter is stopped
When a LPG tank is selected, the tank valve stays opened
The fan is modulating
The gas valve stays opened
When a LPG tank is selected, the tank valve stays opened
When an APS is enabled the APS position is checked
Fan is set to minimum speed
The gas valve stays opened
The fan is set at ignition speed
The gas valve is closed
When a LPG tank is selected, the tank valve is closed
Fan stays at ignition speed
When an APS is enabled the APS position is checked
Blocking error is set
Checking if blocking error can be removed (error situation is solved)
Lockout error is set
User must reset the lockout error (and the controller will reboot)
Finalize processes and reboot the control
The actual fan speed must be within 300RPM of the target fan speed
When the fan speed duty cycle is within the lower/upper 5% of the PWM duty cycle
range no errors will be generated since the fan is in the limits of its working range.
E93.1804.014
:
81