Fiber braid replacement
If the high temp braided rope has discolored or is damaged, it has to be replaced by new braids using the method
described below.
The high temp braided rope is attached to the burner door by silicone glue.
- Remove the braids by sliding under the periphery
a thin tool to loosen the braids and remove it.
- Remove and clean the residues of the braids and
silicone glue.
- Engage the high temp braided rope and place it
in contact of the glue and press the braids.
122
- Put a thin string of temperature-resistant sili-
cone glue in the seal housing. (Loctite 5366 or
Ottoseal S17)
E93.1804.014