Trouble Shooting - intensity MDV-D71T1/VN1-B Installation Manual

High static pressure duct fan & coil
Table of Contents

Advertisement

SW 2 Difinition
SW2
00 means shutting down the unit
ON
to "stop cold air" at 15
1234
01 means shutting down the unit
SW2
ON
to "stop cold air" at 20
1234
SW2
10 means shutting down the unit
ON
to "stop cold air" at 24
1234
SW2
11 means shutting down the unit
ON
to "stop cold air" at 26
1234
SW2
00 means the time of stopping
ON
TERMAL fan is 4 mintue
1234
SW2
01 means the time of stopping
ON
TERMAL fan is 8 mintue
1234
SW2
10 means the time of stopping
ON
TERMAL fan is 12 mintue
1234
SW2
11 means the time of stopping
ON
TERMAL fan is 16 mintue
1234
SW 5 Difinition
SW5
00 means temp. compensation
ON
value is 6
1 2
SW5
01 means temp. compensation
ON
value is 2
1 2
SW5
10 means temp. compensation
ON
value is 4
1 2
SW5
11 means temp. compensation
ON
value is 8
1 2
SW6 Difinition
SW6
1 means old display panel
ON
0 means new display panel
1 2 3
SW6
1 means auto air blow under
auto mode
ON
0 means auto air blow under
non-auto mode
1 2 3
SW6
ON
reserved
1 2 3
SW7 Difinition
SW7
standard
ON
configuration
1 2
SW7
last unit of
ON
the network
1 2
CAUTION
Please adjust the code ENC1 to the suitable position (both
system A and B should be adjusted for 200T1, 250T1 and
280T1 indoor unit).
installation manual
18
under heat mode
under heat mode
under heat mode
under heat mode
0/1 Difinition
ON
means 0
ON
means 1
For 200T1 unit, two mainboards in the electric control
should set the code ENC1 to 8;
For 250T1 unit, a mainboard in the electric control should
set the code ENC1 to 8; the other one should set the code
ENC1 to 9;
For 280T1 unit, two mainboards in the electric control
should set the code to 9.
For the same indoor unit, every mainboard must be differ-
ent indoor unit addresses and network addresses.
When using central controller to control the indoor unit,
please pay attention to the address setting, as the 220T1,
250T1 and 280T1 units have two or more mainboards. We
suggest setting the neighbor address for the mainboards
in the same indoor unit. When using a central controller for
controlling, mainboards in the same unit must be opened
and closed at the same time, for avoiding the unexpected
incident.

13. TROUBLE SHOOTING

Table.13-1
NO. Type
Contents
The evaporator
sensor check
Malfun-
point is abnoma
1
ction
or room temp.
sensor is
abnormal.
Indoor/outdoor unit
Malfun-
communication
2
ction
is abnormal.
Condenser sensor
check point is
Malfun-
abnormal or
3
ction
outdoor temp.
sensor is abnomal
Water level switch
Malfun-
4
is abnormal
ction
5
Alarm
Mode conflict
Malfun-
EPPROM error
6
ction
The indoor unit
without an add-
7
Alarm
ress when it is
first time electri-
fied
LED Lamp flash
Remarks
Run lamp
After the malfunctions
flashes
disappear, it restores
at 2.5Hz.
automatically.
The timer lamp
After the malfunctions
flashes at
disappear, it restores
2.5Hz.
automatically.
After the malfunctions
All the indoor
disappear, it restores
alarm lamps
automatically.
flash at 0.5Hz.
If the malfunctions
can't be solved in
Alarm lamp
three min. all the
flashes
indoor alarm lamps
at 2.5Hz.
flash at 0.5Hz.Turn
off the power to restore.
When the indoor unit
Defrost lamp
turns to heating mode
flashes at
or is turned off, the
2.5Hz.
alarm will disappear.
After the malfunctions
Defrost lamp
flashes at
disappear, it restores
automatically.
0.5Hz.
Timer lamp
After the malfunctions
and run lamp
disappear, it restores
flash at 2.5Hz
automatically.
together.