Refrigerant Pipe Connection - intensity MDV-D71T1/VN1-B Installation Manual

High static pressure duct fan & coil
Table of Contents

Advertisement

Then expose the pipe(cover it with tapes after bending).
To prevent collapsing of deforming, please bend the pipe at its
biggest radius.
Use bender to get a small radius pipes.
Use the market brass pipe.
Be sure to use the same insulating materials when you buy the
brass pipe. (More than 9mm thick)
Use frozen oil
Bend the pipe with thumb
Make the ends
straight
Locate The Pipe
Drill a hole in the wall (suitable just for the size of the wall conduit,
90mm in general), then set on the fittings such as the wall conduit
and its cover.
Bind the connecting pipe and the cables together tightly with
binding tapes. Do not let air in, which will cause water leakage
by condensation.
Pass the bound connecting pipe through the wall conduit from
outside. Be careful of the pipe all ocation to do no damage to the
tubing.
Connect the pipes.
Then, open the stem of stop valves of the outdoor unit to make
the refrigerant pipe connecting the indoor unit with the outdoor
unit fluently flow.
Be sure of no leakage by checking it with leak detector or soap
water.
Cover the joint of the connecting pipe to the indoor unit with the
sound proof/insulating sheath (fittings), and bind it well with the
tapes to prevent leakage.

9. REFRIGERANT PIPE CONNECTION

9.1 Expel The Air
Flaring
Cut a pipe with a pipe cutter.
Insert a flare nut into a pipe and flare the pipe.
installation manual
14
9.2 Check The Leakage
Fig.8-1
Fig.8-2
Fig.8-3
9.3 Insulation
Table.9-1
lean
crude burr
90
Check all the joints with the leak detector or soap water. (See
Fig.9-6 as a reference illustration)
Check-point of indoor unit
Check-point of outdoor unit
A. Lo-stop valve
B. Hi-stop valve
C,D. Joints of the connecting pipe to the indoor unit.
Be sure to with insulating materials cover all the exposed parts
of the flare pipe joints and refrigerant pipe on the liquid-side and
the gas-side. Ensure that there is no gap between them.
Incomplete insulation may cause water condensation.
Outside diameter
6.4mm
12.4
9.5mm
12.7mm
15.8
19.0
15.9mm
19.1mm
23.3
Fig.9-1
D
C
B
A
Fig.9-2
Fig.9-3
A(mm)
Max
Min
8.7
8.3
12.0
15.4
18.6
22.9
Fig.9-4