ROOFTOP PACKAGE TYPE
7.5, 10, 15
20
.
and
Tons
(Convertible)
IPCC090KF-5, IPCC120KF-5, IPCC180KF-5, IPCC240KF-5.
INSTALLATION
& OWNER´S MANUAL
MAN-I-IPCC/5-0217
intensity.mx

Advertisement

Table of Contents
loading

Summary of Contents for intensity IPCC090KF-5

  • Page 1 ROOFTOP PACKAGE TYPE 7.5, 10, 15 Tons (Convertible) IPCC090KF-5, IPCC120KF-5, IPCC180KF-5, IPCC240KF-5. INSTALLATION & OWNER´S MANUAL MAN-I-IPCC/5-0217 intensity.mx...
  • Page 2: General Information

    WARNING ACCESSORIES..................1 Ask your dealer for installation of the air conditioner. GENERAL INFORMATION................1 Incomplete installation performed by yourself may result in a UNIT DIMENSIONS................2 water leakage, electric shock, and fire. LOCATIONS AND RECOMMENDATIONS............4 your dealer improvement, repair, INSTALLATION ..................4 maintenance. ELECTRICAL WIRING................6 Incomplete improvement, repair, and maintenance may result...
  • Page 3: Unit Dimensions

    3. UNIT DIMENSIONS Units: mm 7.5 Tons C/O Units ( Hor. & Dow.) Fig.3-1 Electric heater control box access panel Fresh air Horizontal supply opening Hole for electric heater power wires Horizontal return opening 10 Tons C/O Units ( Hor. & Dow.) Units: mm Fig.3-2 Electric heater control box access panel...
  • Page 4 15 Tons C/O Units ( Hor. & Dow.) Units: mm Fig.3-3 Electric heater control box access panel Horizontal supply opening Hole for electric heater power wires 1029 Fresh air Horizontal return opening 20 Tons C/O Units ( Hor. & Dow.) Units: mm Fig.3-4 Electric heater control box access panel...
  • Page 5: Installation

    4. LOCATIONS AND RECOMMENDATIONS Caution must be taken at all times to avoid personal injuries and/or damage to the equipment. 4.1 Horizontal air ow application The unit must be mounted level for proper drainage of water through the holes in the base pan. When choose horizontal air supply mode, please remove horizontal air supply panel and horizontal air return panel firstly.
  • Page 6: Rooftop-Units

    Spreader bars ≥60° Horizontal Fig.5-1 air deflector 5.2 Rooftop-units Air down return panel Air down flow panel For roof top applications using a field fabricated frame and ducts, use the following procedure: The frame must be located and secured by bolting or welding to the roof.
  • Page 7: Condensate Drain Piping

    5.3 Ground level-horizontal units For ground level installations, the unit should be positioned on a pad in the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure. Be sure the outdoor portion of the supply and return air ducts are as short as possible.
  • Page 8: Electrical Wiring

    6. ELECTRICAL WIRING 6.1 Protections and safety control Minutes delay for the compressor start-up At the beginning of energizing, 3-minutes delay should be WARNING taken to start the compressor. while after the stop of the compressor, 7-minutes delay should be taken to re-start the compressor.
  • Page 9: Error Code

    6.4 Error code Tab.6-2 Type Content Code Remarks Normal Standby Normal Constraint cool Normal Compressor phase sequence Error error or phase default Outdoor coil sensor in sys. A error Error Error Outdoor coil sensor in sys. B error Overcurrent protection of system A are active Unit shall be power off to Error 3 times within one hour...
  • Page 10: Specification

    7. SPECIFICATION 7.1 Physical Data R410A 220V 3Ph~ 60Hz Tab.7- 7.5 Tons Nominal ton Model type Type of flow Hor. & Dow. Cooling capacity(net) (Btu/h) 89000 (Ⅰ) Capacity Heating capacity (Btu/h) Performance Length(mm) Length(mm) 1630 1065 Dimensions Dimensions Width(mm) Width(mm) 1068 Heigth(mm) Heigth(mm)
  • Page 11 R410A 220V 3Ph~ 60Hz ab.7-2 10 Tons Nominal ton Model type Type of flow Hor. & Dow. Cooling capacity(net) (Btu/h) 120000 (Ⅰ) Capacity Heating capacity (Btu/h) Performance 10.5 Length(mm) Length(mm) 2165 Dimensions Dimensions Width(mm) Width(mm) 1335 Heigth(mm) Heigth(mm) 1002 Net weight(kg) Net weight(kg) Refrigerant type Refrigerant type...
  • Page 12 R410A 220V 3Ph~ 60Hz ab.7-3 Nominal ton 15 Tons Model type Hor. & Dow. Type of flow Cooling capacity(net) (Btu/h) 180000 (Ⅰ) Capacity Heating capacity (Btu/h) Performance Length(mm) Length(mm) 2229 Dimensions Dimensions Width(mm) Width(mm) 1825 1245 Heigth(mm) Heigth(mm) Net weight(kg) Net weight(kg) R410A Refrigerant type...
  • Page 13 R410A 220V 3Ph~ 60Hz ab.7-4 20 Tons Nominal ton Model type Type of flow Hor. & Dow. Cooling capacity(net) (Btu/h) 240000 (Ⅰ) Capacity Heating capacity (Btu/h) Performance 10.1 2753 Length(mm) Length(mm) Dimensions Dimensions Width(mm) Width(mm) 2157 Heigth(mm) Heigth(mm) 1245 Net weight(kg) Net weight(kg) Refrigerant type Refrigerant type...
  • Page 14 7.2 Parameter For Air Volume Parameter table for indoor unit air volume ab.7-6 ab.7-5 10 T ons (60Hz) 7.5 T ons (60Hz) Static pressure Air flow Brake power Fan speed Static pressure Air flow Brake power Fan speed (Pa) (CFM) (KW) (rpm) (Pa)
  • Page 15 Curve diagr ram, air flow volumn. 7.5 T ons (60Hz) 10 T ons (60Hz) 2500 2600 2700 2800 2900 3000 3100 3200 3300 3400 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 Air volume(CFM) Air volume(CFM) Fig.7- Fig. 15 T ons (60Hz) 20 T...
  • Page 16: Operating Conditions

    7.3 Operating conditions Parameter table for outdoor unit air volume For proper performance, run the unit under the following temperature conditions: NOTE ab.7-13 S h i e l d p a r t s i n b e l o w t a b l e s a r e s t a n d a r d w o r k i n g Outdoor temperature: 64°F to 125°F conditions for the unit.
  • Page 17 Cooling capacity — 7.5 Tons ab.7-14 Air Flow(CFM) 2600 2800 3000 3200 82.5 84.2 85.8 87.5 87.3 89.0 90.8 92.6 89.3 91.1 92.9 94.8 91.0 92.8 94.7 96.6 72.7 80.4 85.3 87.5 77.4 84.3 88.2 91.1 82.0 84.5 87.9 92.3 86.2 90.3 93.5 95.2 94.8 96.7 98.6 100.6 95.9 97.8 99.8 101.8 96.7 98.6 100.6 102.6 97.3 99.2 101.2 103.3 55.6 68.8 81.8 94.3 58.0 72.6 85.4 96.3 59.5 73.8 88.2 100.1 60.8 75.8 90.7 100.8 98.6 100.6 102.6 104.6 99.2 101.2 103.2 105.2 99.4 101.4 103.4 105.5 99.7 101.7 103.7 105.8...
  • Page 18 Cooling capacity — 10 Tons ab.7-15 Air Flow(CFM) 3000 3400 3800 4200 110.9 113.1 115.4 117.7 113.8 116.1 118.4 120.8 116.5 118.8 121.2 123.6 118.6 121.0 123.4 125.9 96.8 98.7 100.7 102.7 103.2 105.3 107.4 109.5 109.2 111.4 113.6 115.9 114.7 117.0 119.3 121.7 123.4 125.9 128.4 131.0 124.6 127.1 129.6 132.2 125.7 128.2 130.8 133.4 126.3 130.0 131.4 134.0 73.2 92.0 108.3 124.8 75.6 94.3 112.8 128.5 78.0 97.3 116.5 130.4 79.6 99.7 119.4 131.2 127.9 130.5 133.1 135.7 128.3 130.9 133.5 136.2 128.6 131.2 133.8 136.5 129.8 132.4 135.0 137.7...
  • Page 19 Cooling capacity — 15 Tons ab.7-16 Air Flow(CFM) 5400 6000 6600 7200 163.6 165.6 172.9 182.7 168.0 171.6 179.0 188.7 169.9 174.2 185.1 193.6 176.6 179.0 188.8 196.1 138.7 165.6 173.6 183.0 146.1 167.2 177.7 188.2 131.5 155.8 166.0 175.3 185.9 152.3 171.8...
  • Page 20 Cooling capacity — 20 Tons ab.7-17 Air Flow(CFM) 6800 7600 8400 9200 222.0 226.7 236.4 249.3 224.4 230.1 244.6 249.4 216.1 218.7 228.5 241.3 255.8 233.4 236.4 241.8 193.1 223.2 237.2 173.7 205.9 221.6 234.1 183.3 218.7 229.3 248.1 201.2 229.3 242.0 247.8...
  • Page 21: Maintenance

    START-UP Electric heater control box Before starting unit ● Is the unit properly located and level with the proper clearance? ● Is the duct work correctly sized, run, taped, insulated, and weatherproofed with proper unit arrangement? See Ductwork Installation section. Electric heater control box ●...
  • Page 22 ● Re-install the air filter For required to deflection Condenser coil Belt section Unfiltered air circulates through the unit's condenser coil Small pulley Newton(N) Kilogram-force(kgf) can cause the coil's surface to become clogged with diameter (mm) dust, etc. Clean the coil, vertically (i.e., with the fins), and stroke the coil surface with a soft brush.