Put as deep as possible
(about 10mm)
Downward declivity
lower than 1/100
Caution: While connecting the drain pipe, please use the drain pipe con-
nect to the secondary water holder simultaneously, for avoiding
there are little condensate water deposit in the unit when the machine
is running under the high humidity working condition.

11. WIRING

Attaching wiring
The air conditioner should use separate power supply with rated
voltage.
The external power supply to the air conditioner should have
ground wiring, which is linked to the ground wiring of the indoor
and outdoor unit.
The wiring work should be done by qualified persons according
to circuit drawing.
A leakage protector should be installed according to the National
Standard concerning electrical appliance.
Be sure to locate the power wiring and the signal wring well to
avoid cross-disturbance and their contact with connecting pipe
or stop value body.
The wiring attached to this air conditioner is 10m long. Be sure
to prolong it with wiring of the same type and proper length
if necessary. Generally, do not twist two wiring together unless
the joint is soldered well and covered with insulator tape.
Do not turn on the power until you have checked carefully after
wiring.
The Specification of Power
Table.11-1
Capacity(KW)
Phase
Power
Frequency and volt
Circuit breaker/fuse (A)
Indoor unit power wiring (mm
Indoor/outdoor
Ground wiring
connecting
2
Weak electric signal
wiring(mm
)
CAUTION
A disconnection device having an air gap contact separation in
all active conductors should be incorporated in the fixed wiring
according to the National Wiring Regulation.
Communication Wiring Chart
Communication wiring will be different according to the horse-
power of air-condictioners. The wiring of 71T1 to 160T1 indoor
unit, please refer to Fig.11-1, and Fig.11-2 is the communication
wiring for 200T1, 250T1 and 280T1 indoor unit.
installation manual
16
VP30
Fig.10-2
71/80/90/112/140/160
200/250/280
1-Phase
220-240V 50Hz / 208-230V~60HZ
220-240V 50Hz
10/10
16/10
2
)
2.5(<20 m)-4.0(<50 m)
2.0
0.75(<1200 m)
OUTDOOR UNIT
P
Q
E
INDOOR UNIT
INDOOR UNIT
XT2
XT2
X
Y
E
P
Q
X
Y
E
CENTRAL CONTROL
MONITOR
F
F
E
1
2
COMPUTER
OUTDOOR UNIT
P
Q
E
INDOOR UNIT
INDOOR UNIT
XT2 XT3
XT2 XT3
P
Q
E
X
Y
E
X
Y
E
CENTRAL CONTROL
MONITOR
F
F
E
1
2
COMPUTER
CAUTION
The reserved function is indicated in broken line table,users can
select it when necessary.
Terminal board diagram
Please refer to the indoor unit wiring diagram for the detailed
wiring. In accord with the communication wiring, terminal board
wiring is different according to the horsepower of air-condictioners.
The wiring of 71T1 to 160T1 indoor unit, please refer to Fig.11-3,
and Fig.11-4 is the wiring for 200T1, 250T1 and 280T1 indoor unit.
INDOOR UNIT
INDOOR UNIT
XT2
XT2
X
Y
E
E
Fig.11-1
INDOOR UNIT
INDOOR UNIT
XT2
XT3
XT2
P
Q
E
Fig.11-2
XT3

Advertisement

Table of Contents
loading

Table of Contents