Instruction Manual
D104331X012
Table 3. easy-Drive 200L Modbus Map (cont.)
Type
Name
Deadband
uint16
(10=1.0%)
Low travel cutoff position
uint16
(100=10.0%)
Analog on/off close position
uint16
(100=10.0%)
Analog on/off open position
uint16
(100-10.0%)
uint16
Analog Close Value
uint16
Analog Open Value
uint16
Number of retries
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
uint16
Control Source
uint16
Valve Type
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
uint16
RESERVED
MB Register
Default
40053
5
40054
50
40055
400
40056
500
40057
40
40058
200
40059
2
40060
40061
40062
40063
40064
40065
40066
40067
0
40068
1
40069
40070
40071
40072
40073
-continued-
R/W
Values
Minimum percentage signal change to elicit a
movement response based upon end position of last
movement. For example, if the previous command
resulted in the actuator moving to 31.2% of travel and
R/W
0-250
deadband is set to 100 (10.0%), setpoint must
command valve to 21.2% or 41.2% before valve will
move to new position. Default is set set to minimize
signal dithering.
Analog input command, in percent with one implied
decimal (50=5.0%), below this value will result in the
R/W
0-999
valve plug moving to the closed position. Active in
both local and Modbus control modes.
When the valve is in 4-20 mA on/off mode, this value is
the point at which the valve will close. It must be set to
a smaller value than the analog on/off open position.
R/W
0-999
Percentage position value with one implied decimal
(400=40.0%).
When the valve is in 4-20 mA on/off mode, this value is
the point at which the valve will open. It must be set to
a larger value than the analog on/off close position.
R/W
1-1000
Percentage position value with one implied decimal
(500=50.0%).
The analog value, in mA with one implied decimal
R
31 - 220
(40=4.0 mA), that defines the closed position
The analog value , in mA with one implied decimal
R
31 - 220
(200=20.0 mA), that defines the open position
When the valve plug encounters an obstruction, how
many attempts will it make to move past that point,
R/W
0-4
assuming no change in the command signal within the
deadband range
0=Dual Contact On/Off 1=Single Contact On/Off,
R/W
0-5
2=Modbus On/Off, 3=Modbus Positioning,
4=4-20 Positioning, 5=4-20 Level
1=D3, 2=D4, 3=easy-Drive Actuator 0.62",
4=easy-Drive Actuator 0.75", 5 = easy-Drive Actuator
R/W
1-10
Stop-to-Stop, 6 = easy-Drive Actuator 0.50"
easy-Drive 200L
May 2023
Notes
25