easy-Drive 200L
May 2023
Figure 15. Fisher easy-Drive Configuration Software
7. If the Close and Open values are as expected, press Confirm to accept these values. If not, press Cancel to restart
the process.
Note
The value of the 4-20 mA signal must have at least 4 mA difference between the close and open signals. A differential less than
that amount will cause the actuator to reject the calibration and use the previous values.
Should the entered values vary more than 10% from the expected 4-20 mA values; the actuator will accept the calibration and a
Notification displaying "Questionable Analog Calibration" will result.
Figure 16. Fisher easy-Drive Configuration Software

Operational Verification

WARNING
To avoid personal injury or property damage, be aware that the valve will move and respond to an input signal during start
up.