Technical Data; Variants; Accessories - Riello 3470210 Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

Available languages

Available languages

TECHNICAL DATA

MODEL
TYPE
POWER
(1)
OUTPUT
(1)
FUEL
- net calorific value
- density
- viscosity at 20 °C
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATURE
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
MOTOR CAPACITOR
IGNITION TRANSFORMER
PUMP
output (at 12 bar)
pressure range
fuel temperature
ELECTRICAL POWER CONSUMPTION
NOISE LEVEL
SOUND PRESSURE
(2)
SOUND POWER
Reference conditions: Ambient temperature 20°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The
(2)
sound power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy,
as set out in EN ISO 3746.

VARIANTS

Model
RL 34 MZ
RL 44 MZ

ACCESSORIES

:
(optional)
LONG HEAD KIT:
Burner
• CLEAN CONTACT KIT
• KIT POST-PURGING
• KIT HOURCOUNTER
• KIT GROUND FAULT INTERRUPTER
• RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m)
owing to the presence of an INVERTER, or in applications where the length of the thermostat connections exceeds
20 metres, a protection kit is available as an interface between the control box and the burner.
DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a con-
sequence of depressurisation or air leaking past imperfect seals. In double-pipe systems, the air returns to the tank from the return pipe; in single-
pipe systems, the air remains in circulation causing pressure variations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations. Degassing units are provided in two versions:
CODE 3010054 without filter
CODE 3010055 with filter
Degassing unit characteristics
• Burner output
• Light oil pressure
• Ambient temperature
• Light oil temperature
• Attachment connectors
2nd stage
kW
Mcal/h
kg/h
1st stage
kW
Mcal/h
kg/h
LIGHT OIL
kWh/kg
11.8
Mcal/kg
10.2 (10.200 kcal/kg)
0.82 - 0.85
3
kg/dm
/s max 6 (1.5 °E - 6 cSt)
2
mm
• Intermittent (min. 1 stop in 24 hours).
• Two-stage (high and low flame) and single-stage (all - nothing).
number
2
Boilers: water. steam. diathermic oil
°C
0 - 40
°C max
60
V
230 ~ +/-10%
Hz
50/60 - single-phase
rpm
W
V
A
F/V
V1 - V2
I1 - I2
kg/h
bar
°C max
W max
dB(A)
Electrical
Code
supply
3470210
single-phase
3470211
single-phase
3470310
single-phase
3470311
single-phase
3470340
three-phase
3470341
three-phase
RL 34 MZ
Code 3010426
: 80 kg/h max
: 0.7 bar max
: 40 °C max
: 40 °C max
: 1/4 inch
RL 34 MZ
972 T
154 - 395
132 - 340
13 - 33.6
97 - 154
83 - 133
8.3 - 13
2800
300
220 - 240
2.4
12.5/450
230 V - 2 x 12 kV
0.2 A - 30 mA
45
7 - 14
60
600
68
79
Blast tube
length mm
216
351
216
351
216
351
RL 44 MZ
Code 3010425
2
RL 44 MZ
RL 44 MZ
973 T
235 - 485
235 - 485
204 - 418
204 - 418
20 - 41
155 - 235
155 - 235
133 - 204
133 - 204
13 - 20
230 - 400 with neutral ~ +/-10%
50/60 - three-phase
2800
420
230
220/240 - 380/415
2.65
16/425
67
10 - 20
60
700
70
81
973 T
20 - 41
13 - 20
2800
450
2.0 - 1.2
67
10 - 20
60
750
Code 3010419
Code 3010453
Code 3010450
Code 3010448
Code 3010386

Advertisement

Table of Contents
loading

Table of Contents