SELF CHECKING
CALIBRATION CTRL
SIGNAL: XX %
CALIBRATION T°
RIGHT:
XX %
CALIBRATION T°
LEFT:
XX %
CURRENT TIME:
XXXX/XX/XX XX/XX
MFGR TEST DATE:
XX/XXXX
NETWORK UNIT ID:
COM. SPEED: XX bs
DEVICE INST. ID
XXXXXXX
COM. PROTOCOL
Xxxx
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com for up-to-date information.
North America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim
Startup of self-checking system ("YES" or "NO")
Calibration of control signal (-10% to +10%)
Calibration of the tank temperature sensor (-5% to +5%).
Only for RTH with 2 tanks only: Calibration left tempera-
ture (-5% to +5%).
Setting current time (lost when power is off)
"Year/Month/Day
Factory testing date
"Month/Year" (read only)
Address unit network 1 < ID < 254
Communication network speed for RS485
2400 < speed < 230400
This menu allows you to change the BACnet device
instance ID. Value goes from 0 to 4194303, not allowed
value entered would set back to default value = "vendor
ID x 1000 + ThisStationAddress". All 7 digit needs to be
validated to save the value modification.
Network connected: "MODBUS RTU" or "BACNET MS/TP"