HUMIDIFIER
CONFIGURATION
LANGUAGE
Xxxxxxx
CHANGE UNIT TYPE: ERS
XX
CHANGE VOLTAGE:
Xxxxx V
TOTAL GROUP
PROD.: XXKG
DRAINING TYPE:
Xxxxxx
CYCLE DRAIN
DURATION: Xxxx
DRAIN FREQ.:
Xxxxx
COOLING TYPE:
Xxxxxxx
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com for up-to-date information.
42
By pressing enter from this
menu
VALUE: ENGLISH/ FRANÇAIS/ etc.
ERS model (see range)
Selection of power heating: 2x200/2x220/2x-
230/3x200/ 3x208/3x220/3x230/3x380/3x400/
3x415/3x440/3x460/3x480/3x575/3x600/3x690
In case of Master/ Slave control only: adjusts the
total production of the RTH group
Allows to choose the drain logic (CYCLIC BASED or
TIMED BASED)
Setting of drain duration in seconds
Frequency of drain system
IF TIMED BASED: 1 - 255 min
IF CYCLIC BASED: 1 - 10 cycles
Cooling of the tank before service:
2 choices:
"ECO COOLING" (natural cooling, requires several
hours before being able to touch the tank); or
"FAST COOLING" (the temperature of the tank is re-
duced by adding cold water, after few minutes, service
can be done)