Bulletin 539-B HumidiClean ™ Series HC- 6100/6300/6500/6700 Humidifiers Installation, Operation and Maintenance Instructions Table of Contents Page Warning Labels Description of Model Number Installation 5-12 Display Menu 13-16 Start-Up Procedure and Operation 16-17 Maintenance 18-22 Troubleshooting 22-27 Typical Wiring Schematic...
Page 2
SWITCH BEFORE OPENING ANY COVERS AND DOORS! Before servicing the humidifier, learn where the high voltage parts are. KEEP HANDS AND METAL TOOLS AWAY FROM THESE AREAS! Model HC-6100/HC-63000 Series Model HC-6500/HC-67000 Series Warning: All wiring and installation must be completed by qualified personnel only and per the relevant local or national codes on electrical wiring.
Page 3
Warning: Do not operate the supplied humidifier in combustible or explosive surroundings. Warning: Do not operate the supplied humidifier if there is any damage to the cabinet or any components in humidifier are damaged. Warning: The main switch should be a connection breaker which has over current and leakage current protecting functions per code EN60947-3 or EN60947-2 if point gap required by EN60947-3 can be fulfilled.
Page 4
7-1, 7-2, 7-3 and 7-4 located on page 7. Model Description HC - XXXX (DI) - XXX Series HumidiClean™ Humidifiers Type number 6100 6300 6500 6700 Quality of Water Blank: Tap water DI: Deionized or reverse osmosis Rated Power In KW.
Page 5
Figure 5-1 HC-6100/6300 Installation Pitch Min. 1” Per 12” Back to Unit Hose Clamp Steam Hose or Copper Full Size Tee See Detail “A” Hose 2” Insulated Copper 2” Copper Tee “P” Trap Drain Every Soldered Joints 20’ of Piping or at...
Installation HC-6100/6300 Mounting The HumidiClean models HC-6100/6300 are designed to be wall mounted. A wall mounting bracket and lag screws are provided for mounting on 410 mm (16”) centers. The operating weight of the unit is 106 kg (233 lbs). A clearance of 600 mm (23”) on the front and sides of the cabinet is required for servicing. 1. Position wall mounting bracket level on wall and mark hole pattern. Make sure holes line up with studs or other sturdy structure.
Page 7
82 (180) 400/380 30 (68) 98 (216) 130 (288) Drainage Connect HC-6000 drain to suitable waste drainage system. HC-6000 drain water may be as hot as 70°C (158°F). Use clear drain hose provided and 25 mm (1”) copper pipe pitched away from unit at 25 mm (1”) Air Gap inch per foot. An air gap to prevent back flow is required. See Figure 7-1. Figure 7-1 HC-6100/6300/6500/6700...
Page 8
Duct Steam Distribution 1. The dispersion tube should be proper length. Verify correct size from Table 8-1. 2. Install dispersion tube(s) horizontally in duct so holes face upward. Air flow must be vertical up or horizontal. Do not restrict duct with a height of 200 mm (8”) or less. Installations over 10 m/s (1800 FPM) air velocity are not recommended. Consult factory if air flow is vertical down or air velocity is over 10 m/s (1800 FPM). Do not install in ducted systems with static pressure exceeding 150 mm (6”), wc. Airflow should be a minimum of 250 FPM for installations using dispersion tubing. Consult factory if velocity is below recommended level. 3. The dispersion tube(s) should be located upstream of a straight duct run, without obstructions, 3 m (10 feet) or more in length. Consult the factory if this distance is not available. 4. Use the template provided to cut dispersion tube installation holes. Fasten the mounting plate to duct with sheet metal screws. If the dispersion tube is 900 mm (35”) or longer, support the far end with threaded rod or similar means.
Area Steam Distribution The EHF-3 fan package (minimum of 2 required for HC-6500/6700) is designed to be hung on a wall to operate as a remote mounted, direct area discharge option. It incorporates a blower rated at 120v- 1.28 amps. CFM rating is 463 @ 1600 RPM. The fan package requires a separate 120 volt power sup- ply (optional step down transformer available). Consult Armstrong Installation Bulletin IB-95 for more information.
Page 10
Figure 10-1 Standard Humidistat H200-XX-XX-XX H270-XX-XX-XX Supply Main Stat/Sensor In Modulating High Limit Sensor A18609 or Outdoor Temperature Sensor A18610 0-10 Vdc Ground Stat (Standard) Class 2 Alarm A8581 High Limit/ High Limit Air Flow Switch Humidistat Ground A9023 Pressure Switch To Set Up: 1) S1-1, 3 Off, S1-2 On 2) S3-1 On, S3-2, 3, 4 Off...
Page 11
Figure 11-1 0-10 Vdc or 4-20mA Control Signal Supply Main Stat/Sensor In Modulating Control High Limit Sensor Signal Outdoor Temperature Sensor Ground S5079a,b,c 4-20ma Setup 10 vdc Setup 1) S3-1 On, 3-2, 3, 4 Off (Default) 2) S1-2 On, S1-1, 3 Off (Default) 3) S2-1, 2, 3 On if 4-20ma S2-1, 2, 3 All Off If 0-10vdc 4) Select Corresponding Control Signal...
Page 12
High Limit Humidistat Remove the jumper tab from ground and in of high limit/pressure switch connections and wire the high limit stat between these terminals. Refer to Figure10-1 (the overall wiring diagram) for more inform ation. A duct mounted high limit humidistat is recommended to prevent over-saturation of the duct air. Use an on-off controller that opens on fault (high humidity). Humidistat should be set for a maximum of 90% RH. Locate the high limit humidistat approximately 3m (10 feet) downstream of the dispersion manifold. If 3m (10 feet) is not available, consult the factory. Note: High limit humidistat will be wired in series with duct pressure switch, if used, see Figure 10-1.
Display Menu The menu can be accessed via the keypad below the LCD, on the front of electric cabinet. Use the UP or DOWN to change the menu in current level; press ESC to previous menu level; press ENTER to access the current menu. Pressing ENTER will activate selection cursor, press UP(DOWN) to increase (decrease) the value, press ENTER to confirm the change or ESC to cancel. Run Menu Enter to get into main menu Armstrong HC-6000 This screen will only display for 1 minute after the unit is powered up;...
Page 14
Operation Setup Enter Password 0000 (Default) Desired RH (This menu is displayed when RH sensor is selected.) Desired RH: XX% Default: 50% Current RH: XX% LT RT move the cursor UP DN to increase/decrease value Steam Generation Steam Gen (Default) Manual Drain (Status 2 will include Drain Drain.) Manual Fill (Status 2 will include Fill Fill.) Unit Stop...
Page 15
2000 2250 2500 2750 3000 No Beds Operation Setup - Continued Drain Frequency Default: 12 hours 12 (Default) Real Time Time Settings 24 Hour Clock Drain Time 5 (Default) Load Default Reset all to Default? Confirm Cancel Signal Type 0-10 Vdc (Default) 0-5VDC 1.9V - 3.9V 4-20mA...
Page 16
Unit Configuration Enter Password ARMH Run Mode Run (Default) Test Contactor Count Control Type PWM (Default) On/Off Power Settings 1000 W 3000 W 5000 W 6650 W 8000 W EOL Reset Clear Ionic Time Confirm Cancel Failure Record Clear Clear Failure List Confirm Cancel User Password Reset User Password Reset...
Principle of Operation The HumidiClean humidifier converts ordinary tap water or purified water to steam for distribution to raise the relative humidity level. The demand for humidity is sensed by a humidistat or sensor which sends a control signal to the HumidiClean. The HumidiClean is connected to the power supply (208, 220/240, 380/400, 480 or 600 Vac) through a separate circuit breaker supplied by the customer.
Maintenance When 90% of the setting service time has accumulated, the “STATE” LED on the control panel will blink in yellow. (Refer to EOL settings, for bed life duration settings). If the HumidiClean is not serviced at this time; the unit will continue to operate for the remaining 10% of the service life setting. When 100% of the bed life setting has been reached, the “STATE” LED will be on in red. The unit will drain the tank and not respond to a call for demand. Note: Service Life can be adjusted based on water quality. If Ionic Beds are relatively free of scale deposits or scale is forming on tank walls and elements because beds are saturated with scale, please consult the factory for Service Life adjustment procedures.
Page 19
Restoring the Unit to Operation a. Turn power on at breaker. b. Unit should begin to fill. Maximum fill time is approximately 30-45 minutes before contactor(s) will be closed. c. Go into the Operation Setup menu and verify that the unit is in “Steam Gen”. d. See the Unit Configuration menu (Password ARMH) to go to the “EOL (end of life) Reset”.
Page 21
9. Operate the unit configuration menu “EOL Reset”, to reset the ionic bed life. All the accumulated ionic bed time has been reset to zero. The unit should now be heard filling. NOTE: The accumulated ionic bed time can be reset to zero at anytime. However, the unit should not be reset without first inspecting the ionic beds.
Removing the Tank 1. Operate menu to “MANUAL DRAIN” and allow unit to complete a deep drain. (Caution: Tank will still be quite warm). 2. Turn off circuit breaker. 3. Unlock and open front and side doors. Remove left side panel and top panel. 4. Disconnect 3 hoses from front of tank; rubber hose cuff at steam outlet; heating element leads at contactor, fuses, or power module; and thermocouple and aquastat wires. 5.
Page 23
8. If drain valve and fill valve are both energized and water is below the 1/3 full level in the electrode canister (float canister for DI units), make sure the status of Steam Generation in Operation Setup menu is “STEAM GEN.”. Perform continuity check to be sure. 9. If drain valve only is energized and water level is below the 2/3 full level in electrode canister (float canister for DI units), there may be excessive debris in electrode canister (float canister for DI units). Inspect and clean if needed. See page 21 for Cleaning Procedure for Electrodes. 10. PC board may be defective. Consult the factory. Humidifier fills with water, but does not turn “STEAM GEN”...
Page 24
4. If fuses are OK, check voltage to contactor coil. (a) If voltage is 24-28VAC at contactor coil, check coil resistance. It should be 8W with wires disconnected. If resistance is OK, check voltage drops across the contactor. (b) If no voltage to contactor coil, check continuity of wires from PC board to contactor. If continuity is OK, PC board is likely defective. 5. Check voltage signal to power module. The voltage across TAB8-1 and TAB8-2 (low voltage signal to power module) should be 12 Vdc. (a) If no or low voltage, the PC board is likely defective. (b) If voltage is OK, but green “SIGNAL” LED on the power module is not on, power module is defective.
Page 25
Humidifier runs continuously, %RH is well under set-point. 1. Verify humidistat/RH sensor is wired correctly and dip switches (S2 & S3, See Fig. 10-1, 11-1 and 11-1) on the PC board are set correctly for the humidistat signal. 2. Check humidistat demand signal at low voltage terminal strip. It should be close or at 100%. 3. If humidifier is a three phase model, verify all three phases of power are present and equal. 4. Check amperage draw on all high voltage power lines with a clamp on amp meter. They should be same or very close to amperage rating on the humidifier’s nameplate if the humidistat demand is 100%.
Page 26
Dispersion tube spits water or water is present in duct Hint: It is very helpful to cut a small observation window in the duct and cover it with Plexiglas so the steam discharge from the manifold can be observed. This way the problem can be narrowed down to piping/steam quality (steps 1 and 2) or a condensation problem (steps 3 and 4).
Page 27
2 WATER LEVEL DROPPED BELOW LOW LEVEL DURING NORMAL RUN - - The low level switch has not closed after 5 minutes of fill valve on time. This is only after initial start-up fill and boil-down sequence. Check: debris in water switch canister, defective fill valve, no water flow or low water pressure, drain valve stuck open, defective low water level switch (electrodes need to be cleaned).
Page 38
B2716-11 Main PCB For HC-6000 D8025 Hose Clamp, Minerature, Worm B2911-8 Wire Harness For HC-6100 D10872 Kit Fill Valve Assy HC-6100 and HC-6300 Tap Water Wire Harness For HC-6300 D10873 A23520 Tubing Rd 5/8” I.D. Silicon LCD Display For HC-6000...
Page 39
Heating Elements 6100/6300 TC= Thermocouple HC-6100 3kW DI Voltage Without TC With TC Without TC With TC 2PCS/Unit 1PCS/Unit 2PCS/Unit 1PCS/Unit B5808-1 B5809-1 B5810-1 B5811-1 B5808-2 B5809-2 B5810-2 B5811-2 B5808-1 B5809-1 B5810-1 B5811-1 B5808-3 B5809-3 B5810-3 B5811-3 B5808-4 B5809-4 B5810-4 B5811-4...
Page 40
HC6500/6700 Repair Parts Item Item Electrical Compartment Water Compartment Part No. Part No. and Front Panel Label Front Panel With Keypad D10876 PVC Tubing 5/8” A7618A Clap Hose Flat .63 Olive B2716-11 Emergency Stop Button D10866 Main PCB For HC-6000 D8025 Hose Clamp, Minerature, Worm B2911-8...
Page 41
Heating Elements 6500/6700 TC= Thermocouple HC6500/HC6700 30kW 33.5kW 40kW 45kW Voltage Without TC With TC Without TC With TC Without TC With TC Without TC With TC 5PCS/Unit 1PCS/Unit 5PCS/Unit 1PCS/Unit 5PCS/Unit 1PCS/Unit 8PCS/Unit 1PCS/Unit B5433-1 B5434-1 B5433-1 B5434-1 B5433-1 B5434-1 B5433-1 B5434-1 HC6500/HC6700...
Page 42
Resistance Values of Components Resistance Value of 6100/6300 Components Resistance Value of 6500/6700 Components Component Voltage Resistance Component Voltage Resistance Fill Valve 24Vac Fill Valve 24Vac 8.8W Drain Valve 24Vac Drain Valve 24Vac 4.1W Contractor 24Vac 7-9W Thermocouple in Heating Elements 0.51W...
PID Control PID control is essential on the HumidiClean series for maintaining the desired relative humidity (RH) by adjusting the humidifiers output. Please note that the PID control is only used when a RH sensor is supplying the demand in place of a humidistat (configured in Operation Setup Menu). The PID Settings will control how the demand is adjusted according to the error between the current RH and the desired RH set point.
Has an unstable demand (contactor pulling in and out), decrease your proportional band (PB) value or increase your derivative gain (DG) value. Decreasing your PB value will help reach a sta- ble demand, but it will increase the time it takes to reach the desired RH. Another solution to fixing an unstable demand is to increase the DG value. However, if you have any noise in your demand signal, increasing the DG value will only make your unit demand act worse.
Procedure of HC6000 Version 7 Software Update This section is used for HC6000 software reprogramming only. Please follow the instructions carefully, or pc board could become un-functional. 1. Install the driver program for Atmel MCU, SAM-BA on your computer first. The link for the Atmel program AT91-ISP.exe and the latest version of can be found at the following location: www.armstronginternational.com/hc6000refresh 2.
Page 46
Fig. 46-1 Code Download Window d. Click the “open folder” button on the right of textbox “Send File Name” to open the latest code, please see figure 46-2 below. You will then have to locate the .bin file that you downloaded from the website and then hit open.
Page 47
e. Click the button “Send File” to send the latest code into board. You will be asked to unlock the involved lock regions (0 to 7), click the button “Yes” to begin send code into board. Please see figure 47-1 below. Fig. 47-1 Message Unlock Involved Lock Regions Window When sending was finished, you will be asked to lock all locks that you have opened just now, click the button “Yes”...
g. When operation has finished, close the “SAM-BA” window first, and then click the icon “remove the USB hardware” to disconnect the link between computer and board. After reminder by system, disconnect the power supply from breaker and pull out the USB cable. h.
Page 49
be extracted from the protocessor using RUInet. (see Obtaining .xif File using RUInet) 7. A few minutes after the unit is powered on the Initialization LED should light. The protocessor will not communicate until this LED is illuminated. 8. When the Lon device is commissioned the Lon LED on the protocessor will stop blinking and will be on solid.
Page 50
7. The device should be communicating, when using your BMS to modify points the Network Setup has to be set to “Enable” before any other values can be changed. This can be found on the variable list under “Network Enable”. Controlling the Humidifier through Communication Port If you are planning on sending a percent output via communication port follow these instructions.
Page 51
Table 51-1 Modbus Variable Lists Modbus Variants list address description Value / (unit) function number Data Class 10001 Fill valve status 0:off 1:on 10002 Drain valve status 0:off 1:on 10003 contactor 1 status 0:off 1:on function 2 , read 10004 contactor 2 status 0:off 1:on only...
Page 52
Table 52-1. BACnet Variable List BACNet variants list BACnet data type address description Value / (unit) attribute Fill valve status 0:off 1:on Drain valve status 0:off 1:on contactor 1 status 0:off 1:on binary input read only contactor 2 status 0:off 1:on contactor 3 status 0:off 1:on contactor 4 status...
Page 53
Table 53-1. LonWorks Variable List Data Array Map Descriptor Name Data Array Name Lon Function Function Nod Name SNVT Type SNVT Option Offset oFILLSTATUS BITA NVPO Server Lon_1 SNVT_switch state oDRAINSTATUS BITA NVPO Server Lon_1 SNVT_switch state oCON1 BITA NVPO Server Lon_1 SNVT_switch...
Page 54
Physical Data and Dimensional Drawings Figure 54-1. Models HC-6100 and HC-6300 1” Drain Electrical Supply Knock-Out for Humidistat Knock-Out for Humidistat Table 54-1. Physical Data HC-6500, HC-6700 HC-6100 and HC-6300 and HC-6700DI Inches Inches “A”-Width 21-15/16 “B”-Height 32-1/16 56-3/18 1428 “C”-Depth...
Page 55
Physical Data, Capacities and Dimensional Drawings Figure 55-1. Models HC-6500 and HC-6700 — Front, Side, Top Views...
Armstrong International, Inc. Limited Warranty and Remedy Armstrong International, Inc. (“Armstrong”) warrants to the original user of those products supplied by it and used in the service and in the manner for which they are intended, that such products shall be free from defects in material and workmanship for a period of one (1) year from the date of instal- lation, but not longer than 15 months from the date of shipment from the factory, [unless a Special Warranty Period applies, as listed below].