Service; Servicing The Combustion Assembly - Bentone LME21.550C2 Installation And Maintenance Instruction

Hide thumbs Also See for LME21.550C2:
Table of Contents

Advertisement

7. Service

Whoever carries out service and maintenance on the burner must be
authorised to do so. If components need to be replaced, the replacements
must be of the same make and type and be approved by the authorities. If
the burner is to be used for a different grade of gas, a new adjustment must
be carried out. If town gas is to be used, it is also necessary to convert the
combustion assembly; in some cases the multi-block or valves and gas train
may also need to be changed to a larger type.
7.1

Servicing the combustion assembly

Removal and installation
1.
Switch off the main power supply and disconnect the Euro plugs from
the burner.
!
If the burner is directly connected, ensure that all
components on the burner are without power.
2.
Remove the screws (A), turn off the burner Remove the ignition and
ionisation cables
3.
Check the combustion device's position. Remove the screw (B) to
remove the adjustment device.
4.
Remove the screw (C), remove the combustion device.
5.
Check and clean the brake plate and gas inlet. If necessary, replace
the worn parts.
6.
Check the ignition electrode (see chapter Gas nozzle). Replace if
necessary.
7.
Check the ionisation electrode (see chapter Gas nozzle). Replace if
necessary.
8.
Fit the combustion assembly in reverse order.
9.
Press the burner together and lock using the nuts (B).
10.
Fit the Euro plugs and turn on the main power supply.
11.
Check/adjust the combustion.
28
Bentone
172 615 01
2018-01-02

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bg 300