Check code
Compressor current interruption (Locked compressor)
4100
(UF)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Continued from the previous page.
Are they connected properly?
Check whether the compressor is faultily
grounded or not.
Is the compressor faultily grounded?
OCH811A
Diagnosis
Yes
Yes
Connect the wiring properly, then turn the
No
power back ON.
Replace the outdoor power circuit board
No
(Defective outdoor power circuit board).
Replace the compressor (Defective compressor).
73
Chart 2 of 2
Remedy